Trailing & towing
3.3 kV underground roadway distribution, stage-loader drives, crusher skids and mobile mine transformers.
Product
Medium-voltage 1.9/3.3 kV 4-core underground mining feeder cable to MGM 112 and BS 6708 Type 331 featuring three individually copper/nylon-screened EPR phase cores plus one unscreened earth core around a rubber cradle, inner bedding, steel PWA and PCP sheath.
Typical values for this cable type, based on MGM 112 / BS 6708 Type 331 — confirmed in the datasheet and quotation for your order.
Application fit
MGM 112 Type 331 (BS 6708 Type 331) is the dedicated 4-core 1.9/3.3 kV pliable-wire-armoured cable combining individual copper/nylon phase screens with a full internal copper earth core for longwall face distribution and 3.3 kV flameproof switchgear.
3.3 kV underground roadway distribution, stage-loader drives, crusher skids and mobile mine transformers.
Gassy mine gallery cleats, shaft inset distribution and 3.3 kV gate-end box interconnections.
Heavy-duty polychloroprene (RS4/EM2) outer jacket resists wet coal-mine roadways, oil and abrasion.
Pliable wire armour is built for roadway and machine interconnections, not fast crane reeling.
Use (N)TSCGEWÖU ReelingConstruction
Shown: MGM 112 Type 331 3×70+1×35 — 3 EPR-insulated 70 mm² phase cores with individual copper/nylon braid screens + 1 unscreened 35 mm² earth core around a central elastomeric cradle, rubber inner bedding, galvanised steel pliable wire armour (PWA) and black PCP outer sheath.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Tinned copper conductor | Fine-stranded annealed tinned copper wire (IEC 60228 / BS EN 60228 Class 5)IEC 60228 Class 5 |
| 2 | MV EPR core insulation | Cross-linked ethylene-propylene rubber compound Type GP8 (+90 °C rated for 1.9/3.3 kV)BS 7655-1.2 GP8 / MGM 112 |
| 3 | Individual phase screen | Composite tinned-copper and nylon (polyamide) braided earth screen over each of the 3 phase coresMGM 112 / BS 6708 Type 331 |
| 4 | Elastomeric cradle center | Extruded rubber cradle separator keeping the 3 screened phase cores and 1 earth core symmetrically spacedMGM 112 / BS 6708 |
| 5 | Elastomeric inner bedding | Extruded vulcanised rubber inner sheath over the 4-core cradle assemblyMGM 112 inner bedding |
| 6 | Pliable wire armour (PWA) | Stranded galvanised steel wire armour (PWA) providing high crush protection and fault-return conductanceMGM 112 / BS 6708 PWA |
| 7 | Heavy-duty PCP outer sheath | Cross-linked polychloroprene (PCP / Type RS4 / EM2) extra-heavy-duty outer sheath, blackBS 7655-2.1 / IEC 60332-1-2 |
3 individually screened 1.9/3.3 kV phase cores + 1 equal-size earth core around cradle + PWA + PCP sheath
3 individually screened 1.9/3.3 kV phase cores + 1 earth core around cradle + PWA + PCP sheath
Technical data
Sizes
Typical MGM 112 / BS 6708 Type 331 outer diameter limits, copper content and cable weight.
| Order designation | Cores × mm² | AWG ≈ | Outer Ø min mm | Outer Ø max mm | Copper kg/km | Weight ≈ kg/km | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|---|
| MGM 112 Type 331 — 3 Screened Phase + Equal Earth Core (16–25 mm², 1.9/3.3 kV) | ||||||||
| MGM 112 Type 331 3×16+1×16 | 3×16+1×16 | 6 | 35.0 | 38.0 | 730 | 2,450 | 228 | |
| MGM 112 Type 331 3×25+1×25 | 3×25+1×25 | 4 | 38.8 | 42.2 | 1,086 | 3,120 | 253 | |
| MGM 112 Type 331 — 3 Screened Phase + Reduced Earth Core (25–150 mm², 1.9/3.3 kV) | ||||||||
| MGM 112 Type 331 3×25+1×16 | 3×25+1×16 | 4 | 38.5 | 41.8 | 1,000 | 3,040 | 251 | |
| MGM 112 Type 331 3×35+1×25 | 3×35+1×25 | 2 | 41.8 | 45.4 | 1,380 | 3,720 | 272 | |
| MGM 112 Type 331 3×50+1×25 | 3×50+1×25 | 1 | 46.0 | 50.0 | 1,830 | 4,590 | 300 | |
| MGM 112 Type 331 3×70+1×35 | 3×70+1×35 | 2/0 | 50.4 | 54.8 | 2,520 | 5,740 | 329 | |
| MGM 112 Type 331 3×95+1×50 | 3×95+1×50 | 3/0 | 55.4 | 60.2 | 3,420 | 7,120 | 361 | |
| MGM 112 Type 331 3×120+1×70 | 3×120+1×70 | 4/0 | 59.6 | 64.8 | 4,360 | 8,490 | 389 | |
| MGM 112 Type 331 3×150+1×95 | 3×150+1×95 | 300 kcmil | 63.9 | 69.5 | 5,490 | 10,120 | 417 | |
| Cross-section mm² | AWG ≈ | Max. DC resistance 20 °C, Ω/km | 1-core in air 30 °C, A | 3–4 core in air 30 °C, A |
|---|---|---|---|---|
| 16 | 6 | 1.24 | 99 | 82 |
| 25 | 4 | 0.795 | 131 | 108 |
| 35 | 2 | 0.565 | 162 | 135 |
| 50 | 1 | 0.393 | 202 | 168 |
| 70 | 2/0 | 0.277 | 250 | 207 |
| 95 | 3/0 | 0.21 | 301 | 250 |
| 120 | 4/0 | 0.164 | 352 | 292 |
| 150 | 300 kcmil | 0.132 | 404 | 335 |
Reel check
A first screen using datasheet values. Engineering confirms drum geometry, acceleration and tension with your quotation.
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| AC voltage test | 7.5 kV AC (50 Hz) | Every manufactured length |
| Conductor DC resistance | IEC 60228 Class 5 (tinned copper) | Every manufactured length |
| Sample tests | ||
| Vertical flame propagation | IEC 60332-1-2 / EN 60332-1-2 | Per production batch |
| Insulation & sheath elastomer physical properties | MGM 112 / BS 6708 Type 331 | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.