Contact

(F)2XS(FL)2YRAA 19/33 kV Offshore Wind Inter-Array CableVDE 0276-620 · 19/33 kV · Offshore wind inter-array submarine composite cable

(F)2XS(FL)2YRAA 19/33 kV Offshore Wind Inter-Array Cable (DIN VDE 0276-620 / IEC 60502-2) engineered for 19/33 kV service across -20 °C to +90 °C (min. bend radius 15 × OD).

Water-resistant
EMC screen
Outdoor & humid
Approved
Order designation
(F)2XS(FL)2YRAA 3×240 mm² + FO
Outer Ø ≈
118.0 mm
Net weight ≈
26,400 kg/km
Tensile rating ≈
320.0 kN
Core / stranding
IEC 60228 Class 2 water-blocked Cu
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
19/33 kV
Tested per VDE 0276-620
Operating temp.
−20…+90 °C
Continuous subsea & marine service
Min. bend radius
15 × OD
Dynamic sheave & fixed routing
Core / conductor
3×240–630 mm² Cu
Class 2 water-blocked copper + FIMT
Outer protection
Al-PE + SWA + PP
Radial Al-PE moisture barrier
Standard
VDE 0276-620
DIN VDE 0276-620 / IEC 60502-2

Typical values for this cable type, based on DIN VDE 0276-620 / IEC 60502-2 — confirmed in the datasheet and quotation for your order.

Application fit

Is (F)2XS(FL)2YRAA right for your machine?

(F)2XS(FL)2YRAA 19/33 kV Offshore Wind Inter-Array Cable (DIN VDE 0276-620 / IEC 60502-2) engineered for 19/33 kV service across -20 °C to +90 °C (min. bend radius 15 × OD).

Immersion & wet locations

Suitable

Water-blocked core matrix and hydrolysis-resistant subsea jacketing withstand continuous deepwater hydrostatic pressure.

Vertical / spreader reel

Suitable

Torque-balanced aramid or contra-helical steel armour supports vertical winch deployment without hockling.

Offshore platform & shipboard deck trays

Suitable

Marine-grade outer sheath and armour package resist LARS sheave abrasion, UV exposure and salt-spray corrosion.

Trailing & towing

Suitable

High tensile breaking strength supports underwater towing, ROV excursion and seabed plough/trencher duty.

Energy chain / drag chain

Not suitable

Subsea umbilical and tow construction is not intended for high-cycle indoor factory drag chains.

Use Drag-Chain Servo Cable
Typical machinesMarine & Offshore CableWork-Class & Observation ROV SystemsOffshore Wind & Subsea Power GridsOceanographic, Sonar & Seismic SurveyCommercial Diving & Subsea Intervention

Construction

Layer by layer

Shown: (F)2XS(FL)2YRAA (DIN VDE 0276-620 / IEC 60502-2) featuring water-blocked phase cores (3×500 mm²), cu wire screen & al-pe laminate s(fl)2y>c< and hessian & pp roving outer serving (aa) (5-layer construction).

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Water-Blocked Phase Cores (3×500 mm²)Class 2 longitudinal water-blocked Cu (F) + semicon + 8.0 mm 36 kV XLPE (2X)
2Cu Wire Screen & Al-PE Laminate S(FL)2Y>c<25 mm² Cu wire/tape screen + swelling powder (FL) + Al foil laminate + HDPE sheath
3Integrated Subsea FO Cable & PP FillersArmoured single-mode optical cable unit(s) + polypropylene string fillers in valleys
4Galvanized Round Steel Wire Armour (R)54–68 × Ø4.0–4.75 mm galvanized steel wires embedded in bitumen over bedding
5Hessian & PP Roving Outer Serving (AA)Two bitumen-impregnated Hessian tapes + black/yellow polypropylene yarn serving

(F)2XS(FL)2YRAA — Standard Subsea & Marine Execution

Built to DIN VDE 0276-620 / IEC 60502-2 with water-blocked phase cores (3×500 mm²) and hessian & pp roving outer serving (aa)

(F)2XS(FL)2YRAA — Custom Drum Length & Termination Kit

Available in custom continuous subsea/wellbore drum lengths or pre-terminated assemblies

(F)2XS(FL)2YRAA — Routine & Hydrostatic Test Certified

Supplied with EN 10204 3.1 routine dielectric, resistance & pressure/dimensional report

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0276-620 / IEC 60502-2. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / transmission duty
19/33 kV (DIN VDE 0276-620 / IEC 60502-2)
Core / conductor construction
Water-Blocked Phase Cores (3×500 mm²) — Class 2 longitudinal water-blocked Cu (F) + semicon + 8.0 mm 36 kV XLPE (2X)
Primary dielectric / buffering
Cu Wire Screen & Al-PE Laminate S(FL)2Y>c< — 25 mm² Cu wire/tape screen + swelling powder (FL) + Al foil laminate + HDPE sheath

Thermal

Continuous operating temperature
−20…+90 °C (subsea, marine & submersible duty)
Short-circuit / peak thermal rating
Verified thermal stability per DIN VDE 0276-620 / IEC 60502-2
Storage & transport temperature
−40…+80 °C on export wooden/steel drum

Mechanical

Outer protection / armouring
Hessian & PP Roving Outer Serving (AA) — Two bitumen-impregnated Hessian tapes + black/yellow polypropylene yarn serving
Minimum bending radius
15 × OD
Hydrostatic, tensile & crush duty
Galvanized Round Steel Wire Armour (R) — 54–68 × Ø4.0–4.75 mm galvanized steel wires embedded in bitumen over bedding

Resistance

Hydrostatic pressure & water blocking
Engineered for continuous submersion and hydrostatic integrity per DIN VDE 0276-620 / IEC 60502-2
Seawater, oil & chemical resistance
Resistant to seawater hydrolysis, hydraulic oils and abrasion per DIN VDE 0276-620 / IEC 60502-2
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing standard
DIN VDE 0276-620 / IEC 60502-2
Environmental & test standards
IEC 60228 / IEC 60332 / ISO 13628-5 / EN 10204
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
(F)2XS(FL)2YRAA
Sheath colour & metre marking
Continuous metre-marked black outer finish (Al-PE + SWA + PP)
Customs tariff (HS)
8544.49 / 8544.60 / 8544.70

Sizes

3 standard (F)2XS(FL)2YRAA subsea & marine configurations

Manufactured to DIN VDE 0276-620 / IEC 60502-2 for subsea, offshore, deep-well and marine applications.

Dimensions, tensile load & weights
Order designationConfigurationCore / strandingOuter Ø ≈
mm
Net weight ≈
kg/km
Tensile rating
kN ≈
Min. bend R
mm
Enquiry
(F)2XS(FL)2YRAA Construction Schedule (−20…+90 °C)
(F)2XS(FL)2YRAA 3×240 mm² + FO3 × 240 mm² + 48F FIMTIEC 60228 Class 2 water-blocked Cu118.026,400320.01,770
(F)2XS(FL)2YRAA 3×400 mm² + FO3 × 400 mm² + 48F FIMTIEC 60228 Class 2 water-blocked Cu134.034,800420.02,010
(F)2XS(FL)2YRAA 3×630 mm² + FO3 × 630 mm² + 96F FIMTIEC 60228 Class 2 water-blocked Cu152.046,200560.02,280
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Custom core cross-sections, pair/fibre counts, armour grades and factory drum lengths available per DIN VDE 0276-620 / IEC 60502-2.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance, continuity & dimensional verification (DIN VDE 0276-620 / IEC 60502-2)DC resistance at 20 °C / optical attenuation and outer diameter within DIN VDE 0276-620 / IEC 60502-2 tolerancesEvery manufactured drum length
High-voltage dielectric & insulation resistance test (DIN VDE 0276-620 / IEC 60502-2)Zero dielectric breakdown and verified insulation resistance for 19/33 kV ratingEvery manufactured drum length
Sample tests
Hydrostatic pressure, water-blocking & mechanical endurance qualification (DIN VDE 0276-620 / IEC 60502-2)Verified submersion integrity, tensile load and thermal stability across −20…+90 °CType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

VDE 0276-620 CompliantEN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX (F)2XS(FL)2YRAA VDE 0276-620 19/33 kV CE
Delivery form
Heavy-duty export fumigated wooden drums or steel subsea reels
Standard lengths
500 m, 1,000 m or custom continuous subsea/wellbore lengths
MOQ
100 m (standard configurations) · 500 m (custom builds)
Lead time
2–5 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-25
Updated
2026-10-25

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define (F)2XS(FL)2YRAA ((F)2XS(FL)2YRAA 19/33 kV Offshore Wind Inter-Array Cable)?
(F)2XS(FL)2YRAA ((F)2XS(FL)2YRAA 19/33 kV Offshore Wind Inter-Array Cable) is manufactured in accordance with DIN VDE 0276-620 / IEC 60502-2 for 19/33 kV service over -20 °C to +90 °C. Its 5-layer construction comprises water-blocked phase cores (3×500 mm²), cu wire screen & al-pe laminate s(fl)2y>c< and hessian & pp roving outer serving (aa).
What is the minimum bending radius and operating temperature range for (F)2XS(FL)2YRAA?
The minimum bending radius for (F)2XS(FL)2YRAA is 15 × OD across its continuous operating temperature range of -20 °C to +90 °C, ensuring mechanical and dielectric reliability in subsea, marine and submersible service.
How are the concentric layers of (F)2XS(FL)2YRAA arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Water-Blocked Phase Cores (3×500 mm²) — Class 2 longitudinal water-blocked Cu (F) + semicon + 8.0 mm 36 kV XLPE (2X); (02) Cu Wire Screen & Al-PE Laminate S(FL)2Y>c< — 25 mm² Cu wire/tape screen + swelling powder (FL) + Al foil laminate + HDPE sheath; (03) Integrated Subsea FO Cable & PP Fillers — Armoured single-mode optical cable unit(s) + polypropylene string fillers in valleys; (04) Galvanized Round Steel Wire Armour (R) — 54–68 × Ø4.0–4.75 mm galvanized steel wires embedded in bitumen over bedding; (05) Hessian & PP Roving Outer Serving (AA) — Two bitumen-impregnated Hessian tapes + black/yellow polypropylene yarn serving.
What factory test certificates are supplied with (F)2XS(FL)2YRAA?
Every production drum of (F)2XS(FL)2YRAA undergoes routine conductor resistance/continuity, high-voltage dielectric and dimensional testing per DIN VDE 0276-620 / IEC 60502-2, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for (F)2XS(FL)2YRAA

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

(F)2XS(FL)2YRAA 19/33 kV Offshore Wind Inter-Array Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote