Product
CFS1S / CFT1S / CFU1S & KG/KJ/KH/KK Series 150/250 V (BS 6883 / UKOOA Code) GP4 EPR-Insulated Collectively/Individually Screened GSWB-Armoured Type SW4 LSZH Offshore Instrumentation Cable (BS 6883 / UKOOA, 150/250 V, -40 to +90 °C).
Typical values for this cable type, based on BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series) — confirmed in the datasheet and quotation for your order.
Application fit
CFS1S / CFT1S / CFU1S & KG/KJ/KH/KK Series 150/250 V (BS 6883 / UKOOA Code) GP4 EPR-Insulated Collectively/Individually Screened GSWB-Armoured Type SW4 LSZH Offshore Instrumentation Cable (BS 6883 / UKOOA, 150/250 V, -40 to +90 °C).
Individually and/or collectively screened pairs, triads and quads reject electrostatic and electromagnetic interference.
SHF1/SHF2 or IEEE 1580 Type P outer sheath resists drilling mud, hydrocarbons, salt spray and UV exposure.
Compact twisted pairs and numbered cores route cleanly into DCS/PLC cabinets, Ex-i barriers and bridge consoles.
Tinned copper, bronze or galvanized steel wire braid armour protects signal integrity in hazardous offshore zones.
Fixed shipboard and offshore instrumentation cable is not intended for high-speed crane festoon loops.
Use (N)3GRDC5G-J/O Festoon CableConstruction
Shown: CFS1S / CFT1S / CFU1S 250 V (BS 6883 UKOOA) (BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series)) featuring tinned copper epr pairs (5×2×1.5 mm²), individual & collective foil screen (f/ft) and grey type sw4 outer jacket (1s) (5-layer construction).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Tinned Copper EPR Pairs (5×2×1.5 mm²) | BS EN 60228 Class 2/5 tinned copper with GP4 EPR insulation |
| 2 | Individual & Collective Foil Screen (F/F | Al/PET tape + tinned copper drain wire per pair (CFT1S) and overall (CFS1S) |
| 3 | Type SW4 Elastomeric Inner Sheath | Halogen-free low-smoke oil-resistant inner bedding |
| 4 | Galvanized Steel Wire Braid (S - GSWB) | High-tensile galvanized steel wire braid armour |
| 5 | Grey Type SW4 Outer Jacket (1S) | BS 7655 SW4 offshore instrumentation sheath (Grey standard / Blue Ex-i) |
Built to BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series) with tinned copper epr pairs (5×2×1.5 mm²) and grey type sw4 outer jacket (1s)
Available in custom continuous shipboard/offshore drum lengths or with marine EMC cable glands
Supplied with EN 10204 3.1 routine dielectric, conductor resistance & flame/fire test report
Technical data
Sizes
Manufactured to BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series) for shipboard, offshore platform, drilling rig and marine applications.
| Order designation | Configuration | Core / stranding | Outer Ø ≈ mm | Net weight ≈ kg/km | Tensile rating kN ≈ | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|
| CFS1S / CFT1S / CFU1S 250 V (BS 6883 UKOOA) Construction Schedule (−40…+90 °C) | |||||||
| CFS1S 2×2×0.75 mm² | 2 × 2 × 0.75 mm² (2Pr) | Stranded Cu/SnCu (IEC 60228 Class 2/5) | 11.4 | 195 | 1.2 | 70 | |
| CFS1S 4×2×1.0 mm² | 4 × 2 × 1.0 mm² (4Pr) | Stranded Cu/SnCu (IEC 60228 Class 2/5) | 15.6 | 365 | 2.4 | 95 | |
| CFS1S 8×2×1.5 mm² | 8 × 2 × 1.5 mm² (8Pr) | Stranded Cu/SnCu (IEC 60228 Class 2/5) | 22.8 | 760 | 4.8 | 140 | |
| Configuration | Max. DC R₂₀ / Atten. Ω/km or dB/km | Rating / Impedance | Operating temp. |
|---|---|---|---|
| 2 × 2 × 0.75 mm² (2Pr) | 26.00 | 150/250 V (≤60 nF/km) | −40…+90 °C |
| 4 × 2 × 1.0 mm² (4Pr) | 19.50 | 150/250 V (≤65 nF/km) | −40…+90 °C |
| 8 × 2 × 1.5 mm² (8Pr) | 13.30 | 150/250 V (≤75 nF/km) | −40…+90 °C |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance, continuity & dimensional verification (BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series)) | DC resistance at 20 °C / optical attenuation and outer diameter within BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series) tolerances | Every manufactured drum length |
| High-voltage dielectric & insulation resistance test (BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series)) | Zero dielectric breakdown and verified insulation resistance for 150/250 V rating | Every manufactured drum length |
| Sample tests | ||
| Flame, fire integrity, oil/mud & mechanical qualification (BS 6883:1999 & UKOOA Code CFS1S / CFT1S / CFU1S (KG/KH Series)) | Verified flame/fire performance, fluid resistance and thermal stability across −40…+90 °C | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.