Fixed installation
Approved for open cable tray, raceway and supported industrial runs per standard installation rules.
Product
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Typical values for this cable type, based on Reference specification per UL 1569 Type MC / UL 1277 TC-ER (1229528 600V UL 1277 Type MC) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Approved for open cable tray, raceway and supported industrial runs per standard installation rules.
Low-impedance shielding contains high-frequency common-mode currents and dV/dt voltage spikes.
Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.
Outer sheath compound resists industrial cutting fluids, mineral oils and outdoor sunlight.
Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.
Use TRA 0.6/1 kV PUR Reeling CableDurable 600 V XLPE/PVC construction powers industrial process pumps, boosters, and compressor skids under continuous plant duty.
Construction
Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

| # | Layer | Material & reference |
|---|---|---|
| 1 | 3 Phase Conductors (1 AWG Stranded Tinned Cu) | 3×1 AWG (7×19×22) Tinned Copper Phases |
| 2 | XLPE Insulation + 3×6 AWG Symmetrical Grounds | 1.45mm XLPE + 3×6 AWG (7×19×27) Bare Cu Grounds |
| 3 | Dual Helical Bare Copper Tape Shield (100%+100%) | Two Overlapping Helical Bare Copper Tape Shields |
| 4 | Black PVC Inner Jacket + Aluminum Interlocked Armor | Ø30.40 mm PVC Inner Jacket + Helical Aluminum Armor (AIA) |
| 5 | Sunlight & Oil Resistant Black PVC Outer Jacket | UL 1569 Type MC / UL 1277 TC-ER PVC Sheath (38.89 mm OD) |
7×19×22 Tinned Cu + Dual Cu Tape + AIA · Outer diameter 38.89 mm.
7×19×23 Tinned Cu + Dual Cu Tape + AIA · Outer diameter 35.56 mm.
7×19×21 Tinned Cu + Dual Cu Tape + AIA · Outer diameter 41.66 mm.
Technical data
Sizes
Representative configurations from the series specification; select a row to prefill the quotation tool.
| Configuration | Conductor & shield | Insulation / wall | Outer sheath | Outer diameter mm | Min. bend radius mm | Max. conductor resistance @ 20 °C Ω/km | Copper weight kg/km | Cable weight kg/km | Key electrical / optical rating | Part designation | Enquiry |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1229528 600V UL 1277 Type MC | |||||||||||
| 3×1 AWG + 3×6 AWG Sym. GND | 7×19×22 Tinned Cu + Dual Cu Tape + AIA | 1.45mm XLPE + 3×6 AWG (7×19×27) Bare Cu Grounds | Industrial PVC | 38.9 | 467 | 0.41 | 1,685.0 | 2,518 | 600 V (145 A VFD / Dual Cu Tape + AIA) | 1229528 3×1 AWG + 3×6 AWG Sym. GND | |
| 3×2 AWG + 3×8 AWG Sym. GND | 7×19×23 Tinned Cu + Dual Cu Tape + AIA | 1.45mm XLPE + 3×6 AWG (7×19×27) Bare Cu Grounds | Industrial PVC | 35.6 | 427 | 0.52 | 1,310.0 | 2,045 | 600 V (130 A VFD / Dual Cu Tape + AIA) | 1229527 3×2 AWG + 3×8 AWG Sym. GND | |
| 3×1/0 AWG + 3×6 AWG Sym. GND | 7×19×21 Tinned Cu + Dual Cu Tape + AIA | 1.45mm XLPE + 3×6 AWG (7×19×27) Bare Cu Grounds | Industrial PVC | 41.7 | 500 | 0.33 | 2,010.0 | 2,940 | 600 V (170 A VFD / Dual Cu Tape + AIA) | 1229529 3×1/0 AWG + 3×6 AWG Sym. GND | |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance & continuity | Within maximum Ω/km limit at 20 °C | Every manufactured drum length |
| Dielectric withstand / spark test | No breakdown across insulation or shield | Every manufactured drum length |
| Sample tests | ||
| Vertical flame propagation & jacket qualification | Self-extinguishing within standard char limit | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.