Furnace, kiln & high-temp zone
Thermal-rated 1000 V EPDM build delivers stable high-current power near furnaces, ovens, kilns, and molten-metal zones.
Product
WC Hollow-Core 10 kHz Litz braids individually insulated fine bare copper Litz strands around a hollow water-cooling core inside a reinforced EPDM hose to slash skin-effect and proximity losses at up to 10 kHz.
Typical values for this cable type, based on IEC 60317 (Litz) · IEC 60228 Class 6 · DIN VDE 0250 (ref.) — confirmed in the datasheet and quotation for your order.
Application fit
WC Hollow-Core 10 kHz Litz braids individually insulated fine bare copper Litz strands around a hollow water-cooling core inside a reinforced EPDM hose to slash skin-effect and proximity losses at up to 10 kHz.
Thermal-rated 1000 V EPDM build delivers stable high-current power near furnaces, ovens, kilns, and molten-metal zones.
Durable 1000 V EPDM geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Thermal-aged 1000 V EPDM insulation maintains dielectric safety near industrial boilers, ovens, and high-ambient thermal equipment.
Rugged 1000 V EPDM construction handles stationary heavy-plant cable trenches, rolling-mill feeders, and industrial power bays.
1000 V EPDM construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR1000 V EPDM outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.
Use EMC-VFD Submersible EPDMConstruction
Representative construction of WC Hollow-Core 10kHz Litz: IEC 60228 Class 6 extra-flexible bare annealed copper, Individually enamel-insulated copper Litz strands + central coolant hose, and Black reinforced non-conductive EPDM rubber outer hose.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6 |
| 2 | Cooling core / primary dielectric | Individually enamel-insulated copper Litz strands + central coolant hoseIEC 60317 (Litz) |
| 3 | Strength / pressure reinforcement | Non-magnetic textile pressure reinforcement braidIEC 60317 (Litz) |
| 4 | Outer sheath / hose | Black reinforced non-conductive EPDM rubber outer hoseUp to 10 kHz Low Skin Loss |
Single-core high-duty construction protected by Black reinforced non-conductive EPDM rubber outer hose.
Technical data
Sizes
| Cross-section mm² | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 8×D mm |
|---|---|---|---|---|---|
| 1×95 mm² | 39.0 | 0.206 | 912 | 2,445 | 312 |
| 1×150 mm² | 44.3 | 0.129 | 1,440 | 3,544 | 354 |
| 1×240 mm² | 51.3 | 0.080 | 2,304 | 5,305 | 410 |
| 1×300 mm² | 55.2 | 0.064 | 2,880 | 6,456 | 442 |
| 1×400 mm² | 61.0 | 0.049 | 3,840 | 8,362 | 488 |
| 1×500 mm² | 66.1 | 0.038 | 4,800 | 10,250 | 529 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Hydrostatic pressure & dielectric test | 4 kV AC without breakdown | Every manufactured length |
| Continuity & conductor DC resistance | Per IEC 60228 Class 6 at 20 °C | Every drum / assembly |
| Sample tests | ||
| Tensile, dimensional & pressure check | Rated -25 °C to +90 °C continuous | Per production lot |
| Environmental, thermal & mechanical qualification | Up to 10 kHz Low Skin Loss · Insulated Copper Litz Core | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.