Contact

WC Center-Channel 95–500 mm² Water-Cooled Power Cable95–500 mm² flexible copper ropes around a central water-cooling core hose

WC Center-Channel 95–500 arranges fine-stranded bare copper ropes symmetrically around an open central water channel inside a reinforced black EPDM hose for induction furnaces, resistance welders, and heavy rectifiers.

Flame-retardant
Oil-resistant
Approved
Order designation
WC Center-Channel 95-500 Cable 1×240 mm²
Outer Ø
51.3 mm
Max. R20
0.080 Ω/km
Weight
5,305 kg/km
Min. bend R
410 mm
All sizes (8)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
1000 V
Test voltage 3.5 kV AC
Temp. (fixed)
-25°C…+90°C
Flexing: -20 °C to +80 °C
Strength / Armor
Water Hose
Synthetic textile pressure-retaining
Min. bend radius
8 × OD
High-current flexible routing
Conductor
Bare Cu · Cl.6
Per IEC 60228 Class 6
Size range
1×95–1×500
8 standard configurations

Typical values for this cable type, based on IEC 60228 Class 6 · DIN VDE 0250 (ref.) · ISO 1403 Hose — confirmed in the datasheet and quotation for your order.

Application fit

Is WC Center-Channel 95-500 Cable right for your machine?

WC Center-Channel 95–500 arranges fine-stranded bare copper ropes symmetrically around an open central water channel inside a reinforced black EPDM hose for induction furnaces, resistance welders, and heavy rectifiers.

Furnace, kiln & high-temp zone

Suitable

Thermal-rated 1000 V EPDM build delivers stable high-current power near furnaces, ovens, kilns, and molten-metal zones.

Fixed installation

Suitable

Durable 1000 V EPDM geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.

Welding power source & electrode lead

Suitable

Extra-flexible heat- and spatter-resistant 1000 V EPDM build delivers low-drop current to welding tongs and shop floor leads.

High-temperature boiler & thermal plant

Suitable

Thermal-aged 1000 V EPDM insulation maintains dielectric safety near industrial boilers, ovens, and high-ambient thermal equipment.

Energy chain / drag chain

Not suitable

1000 V EPDM construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Immersion & wet locations

Not suitable

1000 V EPDM outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.

Use EMC-VFD Submersible EPDM
Typical machinesElectric arc (EAF) & submerged arc (SAF) steelworksMedium- & high-frequency induction melting foundriesAutomotive robotic spot- & seam-welding linesHeavy DC rectifiers & metallurgical bus feeders

Construction

Layer by layer

Representative construction of WC Center-Channel 95-500 Cable: IEC 60228 Class 6 extra-flexible bare annealed copper, Central open-bore coolant channel with bare copper rope layer, and Black braided-textile reinforced EPDM rubber outer hose.

1234
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorIEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6
2Cooling core / primary dielectricCentral open-bore coolant channel with bare copper rope layerIEC 60228 Class 6
3Strength / pressure reinforcementSynthetic textile pressure-retaining reinforcement braidIEC 60228 Class 6
4Outer sheath / hoseBlack braided-textile reinforced EPDM rubber outer hoseDirect Center Water Cooling

WC Center-Channel 95-500 Cable High-Duty

Single-core high-duty construction protected by Black braided-textile reinforced EPDM rubber outer hose.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on IEC 60228 Class 6 · DIN VDE 0250 (ref.) · ISO 1403 Hose. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
1000 V
Test voltage
3.5 kV AC
Conductor
Bare Cu · Cl.6
Core / dielectric
Central open-bore coolant channel with
Impedance / insulation
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-25 °C to +90 °C
Temp. range (flexing)
-20 °C to +80 °C
Peak / short-circuit
+160 °C (5 s)
Min. bending radius
8 × OD

Resistance

Primary performance
Direct Center Water Cooling
Environment / duty
Zero-Leak Pressure Hose
Mechanical / special
High Flex Fatigue Life
Outer finish
Black braided-textile reinforced EPDM

Sizes

Water-Cooled High-Current Sizes (mm²)
Cross-section
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
8×D mm
1×95 mm²39.00.2069122,445312
1×120 mm²41.60.1611,1522,951333
1×150 mm²44.30.1291,4403,544354
1×185 mm²47.20.1061,7764,233378
1×240 mm²51.30.0802,3045,305410
1×300 mm²55.20.0642,8806,456442
1×400 mm²61.00.0493,8408,362488
1×500 mm²66.10.0384,80010,250529
  • Conductor DC resistance R20 at 20 °C per IEC 60228 Class 6.
  • Minimum bending radius calculated at 8 × nominal outer diameter (OD). Custom terminations available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Hydrostatic pressure & dielectric test3.5 kV AC without breakdownEvery manufactured length
Continuity & conductor DC resistancePer IEC 60228 Class 6 at 20 °CEvery drum / assembly
Sample tests
Tensile, dimensional & pressure checkRated -25 °C to +90 °C continuousPer production lot
Environmental, thermal & mechanical qualificationDirect Center Water Cooling · Zero-Leak Pressure HoseType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

IEC 60228 Class 6DIN VDE 0250 (ref.)ISO 1403 HoseEN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

WC Center-Channel 95-500 Cable 1000 V TEBAOFLEX.COM [IEC 60228 Class 6] [Size] [Metre mark]
Delivery form
Custom assemblies, coils or export drums
Standard lengths
Cut-to-length · 100 m · 500 m · 1,000 m
MOQ
1 assembly / 50 m (stock) · 300 m (custom)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-23
Updated
2026-11-23

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes WC Center-Channel 95-500 Cable suited for demanding 1000 V installations?
WC Center-Channel 95-500 Cable combines IEC 60228 Class 6 extra-flexible bare annealed copper with Central open-bore coolant channel with bare copper rope layer and Black braided-textile reinforced EPDM rubber outer hose. Direct coolant contact along every copper rope achieves 3–4× the ampacity of air-cooled feeders.
What minimum bending radius should be respected for WC Center-Channel 95-500 Cable?
Maintain a minimum bending radius of 8 × OD across -20 °C to +80 °C flexing temperatures to ensure long mechanical and dielectric service life.
Can WC Center-Channel 95-500 Cable be delivered pre-terminated with custom lugs, water fittings, or subsea connectors?
Yes. TEBAOFLEX supplies WC Center-Channel 95-500 Cable either in bulk lengths or factory-assembled with copper lugs, water-cooled swivel fittings, or molded subsea wet-mate connectors.
What quality tests and certificates accompany every shipment of WC Center-Channel 95-500 Cable?
WC Center-Channel 95-500 Cable conforms to IEC 60228 Class 6, DIN VDE 0250 (ref.), ISO 1403 Hose (Direct Center Water Cooling) and ships with an EN 10204 3.1 routine factory test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for WC Center-Channel 95-500 Cable

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

WC Center-Channel 95–500 mm² Water-Cooled Power Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp