Fixed installation
Durable 1.8/3 kV SiR geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Product
Silicone HC 1.8/3 kV pairs Class 6 flexible bare copper (50–400 mm²) with thick corona-resistant black 180 °C halogen-free silicone rubber insulation for traction inverters, induction drives, and hot HV switchgear.
Typical values for this cable type, based on EN 50382 (ref.) · DIN VDE 0250 · IEC 60228 Class 6 — confirmed in the datasheet and quotation for your order.
Application fit
Silicone HC 1.8/3 kV pairs Class 6 flexible bare copper (50–400 mm²) with thick corona-resistant black 180 °C halogen-free silicone rubber insulation for traction inverters, induction drives, and hot HV switchgear.
Durable 1.8/3 kV SiR geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Extra-flexible 1.8/3 kV SiR stranding and 8×D bend radius connect dynamic welding guns, drives, and furnace feeders.
Thermal-aged 1.8/3 kV SiR insulation maintains dielectric safety near industrial boilers, ovens, and high-ambient thermal equipment.
High-capacity 1.8/3 kV SiR feeder connects motor control centers (MCC) cleanly to heavy plant machinery and main distribution panels.
1.8/3 kV SiR construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR1.8/3 kV SiR outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.
Use EMC-VFD Submersible EPDMConstruction
Representative construction of Silicone HC 1.8/3 kV Cable: IEC 60228 Class 6 extra-flexible bare annealed copper, Heavy-wall black 180 °C halogen-free silicone rubber insulation, and Black 1.8/3 kV ozone- & heat-resistant silicone rubber outer sheath.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6 |
| 2 | Heavy-wall extruded insulation | Heavy-wall black 180 °C halogen-free silicone rubber insulationEN 50382 (ref.) |
Single-core extra-flexible high-current conductor inside extruded Black 1.8/3 kV ozone- & heat-resistant silicone rubber outer sheath.
Technical data
Sizes
| Cross-section mm² | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 8×D mm |
|---|---|---|---|---|---|
| 1×50 mm² | 18.9 | 0.386 | 480 | 866 | 151 |
| 1×70 mm² | 20.7 | 0.272 | 672 | 1,166 | 166 |
| 1×95 mm² | 22.6 | 0.206 | 912 | 1,536 | 181 |
| 1×120 mm² | 24.3 | 0.161 | 1,152 | 1,904 | 194 |
| 1×150 mm² | 26.1 | 0.129 | 1,440 | 2,344 | 209 |
| 1×185 mm² | 28.0 | 0.106 | 1,776 | 2,854 | 224 |
| 1×240 mm² | 30.7 | 0.080 | 2,304 | 3,654 | 246 |
| 1×300 mm² | 33.2 | 0.064 | 2,880 | 4,518 | 266 |
| 1×400 mm² | 37.0 | 0.049 | 3,840 | 5,959 | 296 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| High-voltage dielectric withstand test | 6.5 kV AC without breakdown | Every manufactured length |
| Continuity & conductor DC resistance | Per IEC 60228 Class 6 at 20 °C | Every drum / assembly |
| Sample tests | ||
| Tensile, dimensional & pressure check | Rated -60 °C to +180 °C continuous | Per production lot |
| Environmental, thermal & mechanical qualification | 1.8/3 kV Rated Voltage · 180 °C Halogen-Free Silicone | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.