Contact

RD-Y(St)Y Bd PVC-Insulated Paired Electrostatic-Screened Process CableDIN VDE 0815 · 300 V · -30 °C to +70 °C industrial RD-Y(St)Y construction

RD-Y(St)Y Bd PVC-Insulated Paired Electrostatic-Screened Process Control Station Cable (RD-Y(St)Y) engineered to DIN VDE 0815 for 300 V service across -30 °C to +70 °C, featuring stranded bare & tinned copper conductor and pvc outer sheath ral 7032 with

Approved
Low-EMC design
EMC screen
Flame-retardant
Order designation
RD-Y(St)Y 4×2×1.0
Outer Ø ≈
13.5 mm
Total weight ≈
264 kg/km
Min. bend R (fixed)
108 mm
Configuration
4×2×1.0 mm²
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
300 V
Per DIN VDE 0815
Operating temp.
−30…+70 °C
Continuous thermal rating
Min. bend radius
7.5 × OD
Installed / fixed routing
Conductor
bare & tinned
High-conductivity bare & tinned
Outer layer
PVC outer sheath
Extruded PVC outer sheath RAL 7032
Standard
DIN VDE 0815
DIN VDE 0815

Typical values for this cable type, based on DIN VDE 0815 — confirmed in the datasheet and quotation for your order.

Application fit

Is RD-Y(St)Y right for your machine?

RD-Y(St)Y Bd PVC-Insulated Paired Electrostatic-Screened Process Control Station Cable (RD-Y(St)Y) engineered to DIN VDE 0815 for 300 V service across -30 °C to +70 °C, featuring stranded bare & tinned copper conductor and pvc outer sheath ral 7032 with

Fixed installation

Suitable

Engineered and verified for fixed service in accordance with DIN VDE 0815.

Switchgear & control cabinet wiring

Suitable

Engineered and verified for cabinet chassis service in accordance with DIN VDE 0815.

TBM gantry & advancing tunnel reel

With conditions

Use mechanical conduit or armoured protection where exposed to rock fall or crushing loads.

Motorised monospiral reel

Not suitable

Not designed for high-speed monospiral crane reeling; select a dedicated reeling cable.

NSHTOU Reeling Cable
Typical machinesRenewable Energy & EV ChargingAutomated Assembly & Packaging LinesCNC Machine Tools & RoboticsPLC/DCS Control & Marshalling CabinetsIndustrial Drives & Motor ManufacturingHigh-Voltage Grid & Substation Interconnects

Construction

Layer by layer

Shown: RD-Y(St)Y (DIN VDE 0815) with stranded bare & tinned copper conductor, pvc core insulation and pvc outer sheath ral 7032 (5-layer construction).

12345
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Stranded bare & tinned copper conductorHigh-conductivity bare & tinned copper conductor per DIN VDE 0815DIN VDE 0815
2PVC core insulationExtruded PVC dielectric (individual core / group layer)DIN VDE 0815
3Polyester binderHelically applied polyester binderDIN VDE 0815
4Al/polyester overall screenAl/polyester overall screen metallic electromagnetic screen (lapped tape)DIN VDE 0815
5PVC outer sheath RAL 7032Extruded PVC outer sheath RAL 7032 protective layer (continuous layer)DIN VDE 0815

RD-Y(St)Y — Standard Execution

Built to DIN VDE 0815 with stranded bare & tinned copper conductor and pvc outer sheath ral 7032

RD-Y(St)Y — Custom Cross-Sections

Full range of metric mm² and AWG/kcmil conductor sizes per DIN VDE 0815

RD-Y(St)Y — Export Drum Supply

Supplied with EN 10204 3.1 routine dielectric & conductor resistance test certificate

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN VDE 0815. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / duty
300 V (DIN VDE 0815)
Conductor construction
Stranded bare & tinned copper conductor — High-conductivity bare & tinned copper conductor per DIN VDE 0815
Primary insulation / dielectric
PVC core insulation — Extruded PVC dielectric (individual core / group layer)

Thermal

Continuous operating temperature
−30…+70 °C per DIN VDE 0815
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s adiabatic limit depending on dielectric class)
Minimum installation temperature
−5 °C (thermoplastic) / −25 °C (cross-linked or elastomer) / −40 °C (metallic)

Mechanical

Outer protection / covering
PVC outer sheath RAL 7032 — Extruded PVC outer sheath RAL 7032 protective layer (continuous layer)
Minimum bending radius
7.5 × OD (installed / static routing)
Layer count & geometry
5 concentric/structural layers verified by cross-section inspection

Resistance

Environmental & chemical durability
Engineered for industrial service in accordance with DIN VDE 0815
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing product standard
DIN VDE 0815
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
RD-Y(St)Y
Customs tariff (HS)
8544.49 / 8544.60 / 7614.10

Sizes

12 standard RD-Y(St)Y cable configurations

Manufactured to DIN VDE 0815 in single-pair, multi-pair and multi-unit constructions.

Dimensions, construction & weights
Order designationConfigurationOuter Ø ≈
mm
Weight ≈
kg/km
Min. bend R
fixed mm
Enquiry
RD-Y(St)Y Standard Construction Schedule (300 V · −30…+70 °C)
RD-Y(St)Y 1×2×0.51×2×0.5 mm²6.45852
RD-Y(St)Y 2×2×0.52×2×0.5 mm²9.211274
RD-Y(St)Y 4×2×0.54×2×0.5 mm²11.417692
RD-Y(St)Y 8×2×0.58×2×0.5 mm²14.8295118
RD-Y(St)Y 12×2×0.512×2×0.5 mm²17.6420141
RD-Y(St)Y 1×2×1.01×2×1.0 mm²7.68661
RD-Y(St)Y 2×2×1.02×2×1.0 mm²11.016888
RD-Y(St)Y 4×2×1.04×2×1.0 mm²13.5264108
RD-Y(St)Y 8×2×1.08×2×1.0 mm²17.9465143
RD-Y(St)Y 1×2×1.51×2×1.5 mm²8.511468
RD-Y(St)Y 4×2×1.54×2×1.5 mm²15.2348122
RD-Y(St)Y 12×2×1.512×2×1.5 mm²23.4860187
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Additional pair/triad/quad counts (up to 48 pairs) and blue Ex-i intrinsically safe outer sheaths available per DIN VDE 0815.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor DC resistance & dimensional verification (DIN VDE 0815)DC resistance at 20 °C and geometry within DIN VDE 0815 class limitsEvery manufactured drum / spool
Routine dielectric / spark / structural integrity test (DIN VDE 0815)Zero breakdown or structural defect over full production lengthEvery manufactured drum / spool
Sample tests
Thermal aging, mechanical & material qualification (DIN VDE 0815)Full compliance with DIN VDE 0815 across −30…+70 °CType qualification & periodic sample audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0815 CompliantEN 10204 3.1 Routine Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX RD-Y(St)Y <size> DIN VDE 0815 300 V CE
Delivery form
Non-returnable fumigated wooden drums or precision DIN spools
Standard lengths
500 m · 1000 m · 2000 m drums (custom cut lengths on request)
MOQ
500 m (stock sizes) · 1000 m (custom production)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-21
Updated
2026-10-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define RD-Y(St)Y (RD-Y(St)Y Bd PVC-Insulated Paired Electrostatic-Screened Process Control Station Cable)?
RD-Y(St)Y (RD-Y(St)Y Bd PVC-Insulated Paired Electrostatic-Screened Process Control Station Cable) is manufactured in accordance with DIN VDE 0815 for 300 V service over -30 °C to +70 °C. Its 5-layer construction comprises stranded bare & tinned copper conductor, pvc core insulation, polyester binder, al/polyester overall screen, pvc outer sheath ral 7032.
What is the minimum bending radius and installation temperature for RD-Y(St)Y?
The minimum installed bending radius for RD-Y(St)Y is 7.5 × OD across its continuous operating temperature range of -30 °C to +70 °C, ensuring mechanical and dielectric stability without conductor or insulation strain.
How are the concentric layers of RD-Y(St)Y arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Stranded bare & tinned copper conductor (High-conductivity bare & tinned copper conductor per DIN VDE 0815); (02) PVC core insulation (Extruded PVC dielectric (individual core / group layer)); (03) Polyester binder (Helically applied polyester binder); (04) Al/polyester overall screen (Al/polyester overall screen metallic electromagnetic screen (lapped tape)); (05) PVC outer sheath RAL 7032 (Extruded PVC outer sheath RAL 7032 protective layer (continuous layer)).
What factory test certificates are supplied with RD-Y(St)Y?
Every production drum or spool of RD-Y(St)Y undergoes routine conductor DC resistance, dimensional and dielectric/integrity testing per DIN VDE 0815, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for RD-Y(St)Y

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

RD-Y(St)Y Bd PVC-Insulated Paired Electrostatic-Screened Process Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp