Contact

NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium PVC/PVC CableNAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium PVC/PVC Cable manufactured to DIN VDE 0276-603 / IEC 60502-1, rated 0.6/1 kV and -15°C to +70°C with a 12 × OD minimum bending radius for infrastructure & construction installations.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
Oil-resistant
Approved
Order designation
NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium (5G16 mm²)
Outer diameter
22.8 mm
Cable weight
858 kg/km
Min. bend radius
274 mm
Conductor & shield
Class 1/2 Aluminium
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
DIN VDE 0276-603 / IEC 60502-1
Temperature
-15°C to +70°C
Fixed / flex duty
Min. bend radius
12 × OD
22.8–31.5 mm
Screening
Unshielded
Fixed / flex duty
Outer sheath
Industrial PVC
Oil & sunlight resistant
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per DIN VDE 0276-603 / IEC 60502-1 (NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium) — confirmed in the datasheet and quotation for your order.

Application fit

Is NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.

Motor stator, traction & converter leads

Suitable

Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

Offshore platform & shipboard deck trays

Suitable

Outer sheath compound resists industrial oils, moisture ingress, abrasion and outdoor weathering.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use TRA 0.6/1 kV PUR Reeling Cable

Dual-tier power & PLC tray

Suitable

Screened 0.6/1 kV PVC construction suppresses electromagnetic interference on shared industrial power and PLC signal trays.

Typical machinesBuilding & Fire SafetyPower distribution & utility networksRailways, tunnels & public infrastructureProcess instrumentation & oil/gas skidsIndustrial automation & control cabinetsRenewable energy, marine & heavy industry

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
1Conductor5G16 mm² RE/RM Aluminium
2Insulation & Core IdentificationVDE 0276-603 DIV4 PVC core insulation (16 mm² Aluminium)
3Screen / Bedding / Armour LayerUnvulcanised filling compound
4Outer Protective SheathBlack DMV5 flame-retardant PVC outer sheath (OD 22.8 mm)

5G16 mm²

Class 1/2 Aluminium · Outer diameter 22.8 mm

5G25 mm²

Class 1/2 Aluminium · Outer diameter 26.9 mm

5G35 mm²

Class 1/2 Aluminium · Outer diameter 31.5 mm

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per DIN VDE 0276-603 / IEC 60502-1 (NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
0.6/1 kV
Conductor & core insulation
5G16 mm² RE/RM Aluminium · VDE 0276-603 DIV4 PVC core insulation (16 mm² Aluminium)
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
-15°C to +70°C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
DIN VDE 0276-603 / IEC 60502-1

Mechanical

Minimum bending radius
12 × OD
Screening / armour architecture
Unvulcanised filling compound
Outer sheath material & colour
Black DMV5 flame-retardant PVC outer sheath (OD 22.8 mm)

Reference standards

Reference standard
DIN VDE 0276-603 / IEC 60502-1
Hazardous Substance Compliance
CE, UKCA, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Conductor weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium
5G16 mm²Class 1/2 AluminiumVDE 0276-603 DIV4 PVC core insulationIndustrial PVC22.82741.76326.085861 ANAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium (5G16 mm²)
5G25 mm²Class 1/2 AluminiumVDE 0276-603 DIV4 PVC core insulationIndustrial PVC26.93231.13453.71,19481 ANAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium (5G25 mm²)
5G35 mm²Class 1/2 AluminiumVDE 0276-603 DIV4 PVC core insulationIndustrial PVC31.53780.81620.51,633101 ANAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium (5G35 mm²)
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228Every manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation, screen or armourEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing and compliant with reference standard limitsType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0276-603 / IEC 60502-1 CompliantEN 10204 3.1 Factory Test CertificateCE, UKCA, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

NAYY-J / NAYY-O 0.6/1KV VDE 0276-603 ALUMINIUM PVC/PVC CABLE / TEBAOFLEX.COM — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
250 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-04
Updated
2026-11-04

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium designed for?
NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium is engineered for infrastructure & construction installations under DIN VDE 0276-603 / IEC 60502-1, operating over -15°C to +70°C with a minimum bending radius of 12 × OD.
How is NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium constructed across its layers?
Its 4-layer architecture combines 5G16 mm² RE/RM Aluminium with VDE 0276-603 DIV4 PVC core insulation (16 mm² Aluminium), Unvulcanised filling compound and Black DMV5 flame-retardant PVC outer sheath (OD 22.8 mm).
What standards and routine factory tests apply to NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium?
Every manufactured drum is tested to DIN VDE 0276-603 / IEC 60502-1 for conductor continuity, dielectric voltage withstand and sheath integrity, supplied with an EN 10204 3.1 inspection certificate.
What sizes and drum lengths are available for NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium?
Representative sizes include 5G16 mm², 5G25 mm² and 5G35 mm², supplied on 250 m, 500 m or 1,000 m export drums or custom cut lengths.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

NAYY-J / NAYY-O 0.6/1kV VDE 0276-603 Aluminium PVC/PVC Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote