NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV Transformer Lead CableNF C 33-224 / NF C 33-225 3.6/6kV–6/10kV Transformer Lead Cable manufactured to NF C 33-224 / NF C 33-225, rated 3.6/6 (7.2) kV / 6/10 (12) kV and -25°C to +90°C with a 15 × OD minimum bending radius for renewable energy installations.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
Outdoor & humid
Approved
Order designation
NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV (1×95 mm²)
Outer diameter
22.4 mm
Cable weight
1,179 kg/km
Min. bend radius
336 mm
Conductor & shield
Stranded Tinned Copper
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
3.6/6–6/10 kV
NF C 33-224 / NF C 33-225
Temperature
-25°C to +90°C
Fixed / flex duty
Min. bend radius
15 × OD
22.4–30.9 mm
Screening
Unshielded
Fixed / flex duty
Outer sheath
Elastomer Jacket
Heavy-duty thermoset elastomer
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per NF C 33-224 / NF C 33-225 (NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV) — confirmed in the datasheet and quotation for your order.

Application fit

Is NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.

Motor stator, traction & converter leads

Suitable

Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

Offshore platform & shipboard deck trays

Suitable

Outer sheath compound resists industrial oils, moisture ingress, abrasion and outdoor weathering.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use WXG / WXG-D MV Reeling Cable

Substation MV/HV underground duct bank

Suitable

High-dielectric 6/10 kV XLPE construction feeds medium- and high-voltage substation duct banks, transformer bays, and utility feeders.

Typical machinesRenewable Energy & EV ChargingPower distribution & utility networksRailways, tunnels & public infrastructureProcess instrumentation & oil/gas skidsIndustrial automation & control cabinetsRenewable energy, marine & heavy industry

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
1Conductor1×95 mm² Stranded Tinned/Bare Cu
2Insulation & Core IdentificationNF C 33-225 thick-wall 6/10kV XLPE dielectric over semi-con screen (95 mm² TC)
3Screen / Bedding / Armour LayerSemi-conducting separator tape
4Outer Protective SheathRed cross-linked XLPE / elastomer outer sheath (10 kV Red ID, OD 22.4 mm)

1×95 mm²

Stranded Tinned Copper · Outer diameter 22.4 mm

1×120 mm²

Stranded Tinned Copper · Outer diameter 26.4 mm

1×150 mm²

Stranded Tinned Copper · Outer diameter 30.9 mm

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per NF C 33-224 / NF C 33-225 (NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
3.6/6 (7.2) kV / 6/10 (12) kV
Conductor & core insulation
1×95 mm² Stranded Tinned/Bare Cu · NF C 33-225 thick-wall 6/10kV XLPE dielectric over semi-con screen (95 mm² TC)
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
-25°C to +90°C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
NF C 33-224 / NF C 33-225

Mechanical

Minimum bending radius
15 × OD
Screening / armour architecture
Semi-conducting separator tape
Outer sheath material & colour
Red cross-linked XLPE / elastomer outer sheath (10 kV Red ID, OD 22.4 mm)

Reference standards

Reference standard
NF C 33-224 / NF C 33-225
Hazardous Substance Compliance
CE, UKCA, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Copper weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV
1×95 mm²Stranded Tinned CopperNF C 33-225 thick-wall 6/10kV XLPE dielectric overElastomer Jacket22.43360.19613.11,179244 ANF C 33-224 / NF C 33-225 3.6/6kV–6/10kV (1×95 mm²)
1×120 mm²Stranded Tinned CopperNF C 33-225 thick-wall 6/10kV XLPE dielectric overElastomer Jacket26.43960.15853.81,642282 ANF C 33-224 / NF C 33-225 3.6/6kV–6/10kV (1×120 mm²)
1×150 mm²Stranded Tinned CopperNF C 33-225 thick-wall 6/10kV XLPE dielectric overElastomer Jacket30.94640.121,167.92,246324 ANF C 33-224 / NF C 33-225 3.6/6kV–6/10kV (1×150 mm²)
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228Every manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation, screen or armourEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing and compliant with reference standard limitsType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

NF C 33-224 / NF C 33-225 CompliantEN 10204 3.1 Factory Test CertificateCE, UKCA, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

NF C 33-224 / NF C 33-225 3.6/6KV–6/10KV TRANSFORMER LEAD CABLE / TEBAOFLEX.COM — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
250 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-04
Updated
2026-11-04

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV designed for?
NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV is engineered for renewable energy installations under NF C 33-224 / NF C 33-225, operating over -25°C to +90°C with a minimum bending radius of 15 × OD.
How is NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV constructed across its layers?
Its 4-layer architecture combines 1×95 mm² Stranded Tinned/Bare Cu with NF C 33-225 thick-wall 6/10kV XLPE dielectric over semi-con screen (95 mm² TC), Semi-conducting separator tape and Red cross-linked XLPE / elastomer outer sheath (10 kV Red ID, OD 22.4 mm).
What standards and routine factory tests apply to NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV?
Every manufactured drum is tested to NF C 33-224 / NF C 33-225 for conductor continuity, dielectric voltage withstand and sheath integrity, supplied with an EN 10204 3.1 inspection certificate.
What sizes and drum lengths are available for NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV?
Representative sizes include 1×95 mm², 1×120 mm² and 1×150 mm², supplied on 250 m, 500 m or 1,000 m export drums or custom cut lengths.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

NF C 33-224 / NF C 33-225 3.6/6kV–6/10kV Transformer Lead Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote