NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 manufactured to DIN VDE 0276-603 / HD 603 / IEC 60502-1, rated 0.6/1 kV – 1.8/3 kV and -25°C to +90°C with a 15 × OD minimum bending radius for renewable energy installations.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
Oil-resistant
Approved
Order designation
NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 (4G35 mm²)
Outer diameter
25.0 mm
Cable weight
1,031 kg/km
Min. bend radius
375 mm
Conductor & shield
Class 2 Compacted Stranded Aluminium
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1–1.8/3 kV
DIN VDE 0276-603 / HD 603 / IEC 60502-1
Temperature
-25°C to +90°C
Fixed / flex duty
Min. bend radius
15 × OD
25.0–34.5 mm
Screening
Unshielded
Fixed / flex duty
Outer sheath
Industrial PVC
Oil & sunlight resistant
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per DIN VDE 0276-603 / HD 603 / IEC 60502-1 (NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603) — confirmed in the datasheet and quotation for your order.

Application fit

Is NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.

Motor stator, traction & converter leads

Suitable

Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

Offshore platform & shipboard deck trays

Suitable

Outer sheath compound resists industrial oils, moisture ingress, abrasion and outdoor weathering.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use TRA 0.6/1 kV PUR Reeling Cable

Dual-tier power & PLC tray

Suitable

Screened 1.8/3 kV XLPE/PVC construction suppresses electromagnetic interference on shared industrial power and PLC signal trays.

Typical machinesRenewable Energy & EV ChargingPower distribution & utility networksRailways, tunnels & public infrastructureProcess instrumentation & oil/gas skidsIndustrial automation & control cabinetsRenewable energy, marine & heavy industry

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
1Conductor4G35 mm² RM Class 2 Stranded Al
2Insulation & Core IdentificationVDE 0276-603 2XI1 XLPE core insulation (35 mm² Class 2 Aluminium)
3Screen / Bedding / Armour LayerUnvulcanised inner filling compound
4Outer Protective SheathBlack DMV5 flame-retardant PVC outer sheath (OD 25.0 mm)

4G35 mm²

Class 2 Compacted Stranded Aluminium · Outer diameter 25.0 mm

4G50 mm²

Class 2 Compacted Stranded Aluminium · Outer diameter 29.5 mm

4G70 mm²

Class 2 Compacted Stranded Aluminium · Outer diameter 34.5 mm

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per DIN VDE 0276-603 / HD 603 / IEC 60502-1 (NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
0.6/1 kV – 1.8/3 kV
Conductor & core insulation
4G35 mm² RM Class 2 Stranded Al · VDE 0276-603 2XI1 XLPE core insulation (35 mm² Class 2 Aluminium)
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
-25°C to +90°C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
DIN VDE 0276-603 / HD 603 / IEC 60502-1

Mechanical

Minimum bending radius
15 × OD
Screening / armour architecture
Unvulcanised inner filling compound
Outer sheath material & colour
Black DMV5 flame-retardant PVC outer sheath (OD 25.0 mm)

Reference standards

Reference standard
DIN VDE 0276-603 / HD 603 / IEC 60502-1
Hazardous Substance Compliance
CE, UKCA, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Conductor weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603
4G35 mm²Class 2 Compacted Stranded AluminiumVDE 0276-603 2XI1 XLPE core insulationIndustrial PVC25.03750.81391.81,031101 ANA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 (4G35 mm²)
4G50 mm²Class 2 Compacted Stranded AluminiumVDE 0276-603 2XI1 XLPE core insulationIndustrial PVC29.54420.56545.71,436122 ANA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 (4G50 mm²)
4G70 mm²Class 2 Compacted Stranded AluminiumVDE 0276-603 2XI1 XLPE core insulationIndustrial PVC34.55180.40746.31,964155 ANA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 (4G70 mm²)
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228Every manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation, screen or armourEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing and compliant with reference standard limitsType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN VDE 0276-603 / HD 603 / IEC 60502-1 CompliantEN 10204 3.1 Factory Test CertificateCE, UKCA, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

NA2XY-J / NA2XY-O 0.6/1KV–1.8/3KV VDE 0276-603 / TEBAOFLEX.COM — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
250 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-04
Updated
2026-11-04

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 designed for?
NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 is engineered for renewable energy installations under DIN VDE 0276-603 / HD 603 / IEC 60502-1, operating over -25°C to +90°C with a minimum bending radius of 15 × OD.
How is NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603 constructed across its layers?
Its 4-layer architecture combines 4G35 mm² RM Class 2 Stranded Al with VDE 0276-603 2XI1 XLPE core insulation (35 mm² Class 2 Aluminium), Unvulcanised inner filling compound and Black DMV5 flame-retardant PVC outer sheath (OD 25.0 mm).
What standards and routine factory tests apply to NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603?
Every manufactured drum is tested to DIN VDE 0276-603 / HD 603 / IEC 60502-1 for conductor continuity, dielectric voltage withstand and sheath integrity, supplied with an EN 10204 3.1 inspection certificate.
What sizes and drum lengths are available for NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603?
Representative sizes include 4G35 mm², 4G50 mm² and 4G70 mm², supplied on 250 m, 500 m or 1,000 m export drums or custom cut lengths.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

NA2XY-J / NA2XY-O 0.6/1kV–1.8/3kV VDE 0276-603

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote