Quayside shore-to-ship HVSC connection
IEC/IEEE 80005-1 compliant HVSC electro-optical design supplies clean berth power with integrated pilot and fibre cores.
Product
HVSC 6/10 kV & 8.7/15 kV (IEC/IEEE 80005-1) Three-Core MV Power with Split Earth, 24-Fiber Optic & Pilot Cores Anti-Torsion Polychloroprene Shore-to-Ship Reeling Cable (IEC/IEEE 80005-1, 6/10 kV – 8.7/15 kV, -40 to +90 °C).
Typical values for this cable type, based on IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813 — confirmed in the datasheet and quotation for your order.
Application fit
HVSC 6/10 kV & 8.7/15 kV (IEC/IEEE 80005-1) Three-Core MV Power with Split Earth, 24-Fiber Optic & Pilot Cores Anti-Torsion Polychloroprene Shore-to-Ship Reeling Cable (IEC/IEEE 80005-1, 6/10 kV – 8.7/15 kV, -40 to +90 °C).
IEC/IEEE 80005-1 compliant HVSC electro-optical design supplies clean berth power with integrated pilot and fibre cores.
Integrated anti-torsion braid and flexible Class 5 conductors withstand continuous motorized reeling and tensioning.
Top-drive service loop execution handles continuous vertical flexing, torsion and ester drilling mud splash in the derrick.
Heavy-duty polychloroprene / CSP / Type P outer sheath resists seawater immersion, quayside abrasion, oil and UV.
Heavy shore-power and derrick reeling cable is not intended for small-radius indoor factory drag chains.
Use Drag-Chain Servo CableConstruction
Shown: HVSC 6/10 & 8.7/15 KV (IEC 80005-1) (IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813) featuring hvsc mv phase cores (3×95 mm²), interstitial split earth conductors and double 5gm5 polychloroprene sheath (5-layer construction).
| # | Layer | Material & reference |
|---|---|---|
| 1 | HVSC MV Phase Cores (3×95 mm²) | Class 5 tinned copper with triple-extruded EPR insulation (6/10–8.7/15 kV) |
| 2 | Interstitial Split Earth Conductors | Flexible tinned copper earth cores in outer interstices |
| 3 | IEC 80005-1 Fiber-Optic & Pilot Unit | Integrated optical fiber & pilot control sub-unit for shore-ship interlock |
| 4 | Anti-Torsion Reinforcement Braid | Embedded synthetic anti-torsion braid between inner and outer sheaths |
| 5 | Double 5GM5 Polychloroprene Sheath | Heavy-duty oil-, seawater- and abrasion-resistant reeling jacket |
Built to IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813 with hvsc mv phase cores (3×95 mm²) and double 5gm5 polychloroprene sheath
Available in custom continuous shipboard/offshore drum lengths or with marine EMC cable glands
Supplied with EN 10204 3.1 routine dielectric, conductor resistance & flame/fire test report
Technical data
Sizes
Manufactured to IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813 for shipboard, offshore platform, drilling rig and marine applications.
| Order designation | Configuration | Core / stranding | Outer Ø ≈ mm | Net weight ≈ kg/km | Tensile rating kN ≈ | Min. bend R mm | Enquiry |
|---|---|---|---|---|---|---|---|
| HVSC 6/10 & 8.7/15 KV (IEC 80005-1) Construction Schedule (−40…+90 °C) | |||||||
| HVSC 6/10 & 8.7/15 KV 3×70+2G25+24F | 3×70 + 2×25 mm² + 2×Pilot + 24F | IEC 60228 Class 5 flexible Cu/SnCu | 58.0 | 5,420 | 31.5 | 580 | |
| HVSC 6/10 & 8.7/15 KV 3×95+2G35+24F | 3×95 + 2×35 mm² + 2×Pilot + 24F | IEC 60228 Class 5 flexible Cu/SnCu | 63.5 | 6,780 | 42.8 | 635 | |
| HVSC 6/10 & 8.7/15 KV 3×150+2G50+24F | 3×150 + 2×50 mm² + 2×Pilot + 24F | IEC 60228 Class 5 flexible Cu/SnCu | 72.4 | 9,350 | 67.5 | 725 | |
| Configuration | Max. DC R₂₀ / Atten. Ω/km or dB/km | Rating / Impedance | Operating temp. |
|---|---|---|---|
| 3×70 + 2×25 mm² + 2×Pilot + 24F | 0.27 | 6/10 kV – 8.7/15 kV (245 A HVSC) | −40…+90 °C |
| 3×95 + 2×35 mm² + 2×Pilot + 24F | 0.19 | 6/10 kV – 8.7/15 kV (300 A HVSC) | −40…+90 °C |
| 3×150 + 2×50 mm² + 2×Pilot + 24F | 0.12 | 6/10 kV – 8.7/15 kV (385 A HVSC) | −40…+90 °C |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance, continuity & dimensional verification (IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813) | DC resistance at 20 °C / optical attenuation and outer diameter within IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813 tolerances | Every manufactured drum length |
| High-voltage dielectric & insulation resistance test (IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813) | Zero dielectric breakdown and verified insulation resistance for 6/10 kV – 8.7/15 kV rating | Every manufactured drum length |
| Sample tests | ||
| Flame, fire integrity, oil/mud & mechanical qualification (IEC/IEEE 80005-1 High-Voltage Shore Connection (HVSC) / DIN VDE 0250-813) | Verified flame/fire performance, fluid resistance and thermal stability across −40…+90 °C | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.