Fixed installation
Counter-helical Double Wire Armour supports vertical shaft suspension and resists severe roadway rock-fall crush.
Product
MGM 109 Type 3123 Cable is the highest-integrity 1.9/3.3 kV underground mining roadway and shaft feeder cable to British Coal Specification MGM 109 and BS 6708, combining three Class 2 tinned copper phase conductors (16 mm² to 185 mm²), 90 °C Type GP4 EPR
Typical values for this cable type, based on British Coal MGM 109 / BS 6708 (Type 3123 1.9/3.3 kV Screened DWA) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for 3.3 kV longwall coal-face supply gates, vertical mine shafts, incline drifts, and sensitive earth-leakage protected underground networks where both individual core screening and
Counter-helical Double Wire Armour supports vertical shaft suspension and resists severe roadway rock-fall crush.
Individual copper phase screens convert any internal insulation damage into a low-energy earth fault before a phase-to-phase arc can
PVC inner bedding, bitumen/compound anti-corrosion treatment, and thick outer PVC jacket resist corrosive mine water.
Fixed double-armoured 3.3 kV shaft/roadway feeder.
MGM 109 Type 3023Construction
Three circular stranded tinned copper conductors (BS EN 60228 Class 2, 16 to 185 mm²), 90 °C Type GP4 EPR insulation, individual helically
| # | Layer | Material & reference |
|---|---|---|
| 1 | Stranded tinned copper conductor | BS EN 60228 Class 2 circular stranded tinned annealed copper (16 to 185 mm²)MGM 109 / BS EN 60228 |
| 2 | Type GP4 EPR rubber insulation (90 °C) | Cross-linked ethylene-propylene elastomer Type GP4 per BS 7655-1.2MGM 109 / BS 7655-1.2 |
| 3 | Individual tinned copper tape phase | Helically lapped tinned annealed copper tape over each insulated core in contact withMGM 109 Type 3123 |
| 4 | Extruded PVC inner bedding | Flame-retardant extruded PVC inner beddingMGM 109 |
| 5 | Double Wire Armour (DWA ≥ 75 % | Two counter-helical layers of galvanized steel wires (+ tinned Cu wires) with jute/tapeMGM 109 / BS 6708 |
| 6 | Mining flame-retardant PVC outer sheath | Heavy-duty abrasion- and flame-retardant PVC outer sheath, BlackMGM 109 / BS 7655 |
1.9/3.3 kV individually copper-screened DWA feeders for auxiliary transformers and stage loaders.
High-capacity 3.3 kV screened DWA trunk cables with composite Cu/GSW armour.
Technical data
Sizes
Nominal dimensions, copper weights, DC resistance and current ratings for MGM 109 Type 3123 per British Coal MGM 109 / BS 6708 (Type 3123 1.9/3.3 kV Screened
| Order designation | Cores × Size | Main cross-section | Outer Ø ≈ mm | Copper kg/km | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|---|---|
| Standard MGM 109 Type 3123 configurations | |||||||
| MGM 109 Type 3123 3C × 25 mm² Cu-Scr DWA | 3 × 25 mm² | 25.0 mm² | 36.8 | 920 | 2,950 | 442 | |
| MGM 109 Type 3123 3C × 50 mm² Cu-Scr DWA | 3 × 50 mm² | 50.0 mm² | 43.2 | 1,690 | 4,280 | 518 | |
| MGM 109 Type 3123 3C × 70 mm² Cu-Scr DWA | 3 × 70 mm² | 70.0 mm² | 47.6 | 2,340 | 5,360 | 571 | |
| MGM 109 Type 3123 3C × 95 mm² Cu-Scr DWA | 3 × 95 mm² | 95.0 mm² | 52.4 | 3,180 | 6,690 | 629 | |
| MGM 109 Type 3123 3C × 120 mm² Cu-Scr DWA | 3 × 120 mm² | 120.0 mm² | 56.8 | 3,980 | 7,940 | 682 | |
| MGM 109 Type 3123 3C × 185 mm² Cu-Scr DWA | 3 × 185 mm² | 185.0 mm² | 65.4 | 6,080 | 10,980 | 785 | |
| Configuration | Max. DC R @ 20 °C Ω/km | Iz free air A | Iz tray / duct A | Isc (1 s) kA | Voltage drop mV/A/m | Dielectric test V |
|---|---|---|---|---|---|---|
| 3 × 25 mm² | 0.73 | 131 | 118 | 3.58 | 1.56 | 6,500 |
| 3 × 50 mm² | 0.39 | 192 | 173 | 7.15 | 0.82 | 6,500 |
| 3 × 70 mm² | 0.27 | 238 | 214 | 10.01 | 0.58 | 6,500 |
| 3 × 95 mm² | 0.20 | 288 | 259 | 13.59 | 0.43 | 6,500 |
| 3 × 120 mm² | 0.15 | 332 | 299 | 17.16 | 0.35 | 6,500 |
| 3 × 185 mm² | 0.10 | 430 | 387 | 26.46 | 0.24 | 6,500 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| 6.5 kV AC dielectric & insulation resistance | 6,500 V AC for 5 min core-to-screen & core-to-armour | 100 % of drums |
| Phase, Cu screen & DWA DC resistance | Combined metallic earth conductance ≥ 75 % of one phase core | 100 % of drums |
| Sample tests | ||
| GP4 EPR hot-set & armour wire torsion/zinc test | BS 7655-1.2 & BS EN 10257-1 compliance | Per production batch |
| Mining impact crush & flame propagation test | Pass MGM 109 / BS 6708 roadway qualification | Type approval |
Marking & supply
Sheath marking