Fixed installation
Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.
Product
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Typical values for this cable type, based on Reference specification per NBN HD 620-10C / Synergrid (EAXCG / EAXCWB / EAXCVB 0.6/1kV–8.7/15kV NBN) — confirmed in the datasheet and quotation for your order.
Application fit
Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.
Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.
Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.
Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.
Low-smoke zero-halogen outer sheath minimizes toxic acid gas emission and smoke obscuration in fire events.
Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.
Use WXG / WXG-D MV Reeling CableHigh-dielectric 8.7/15 kV XLPE/LSZH construction feeds medium- and high-voltage substation duct banks, transformer bays, and utility feeders.
Construction
Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | 1×150/25 mm² Class 2 Compacted Al |
| 2 | Insulation & Core Identification | NBN HD 620 XLPE dielectric (150 mm² Class 2 Compacted Aluminium) |
| 3 | Screen / Bedding / Armour Layer | Semi-conductive longitudinal water-blocking tape + Helical copper wire screen + copper equalising tape |
| 4 | Outer Protective Sheath | Red Low Smoke Zero Halogen (LSZH) outer sheath (OD 30.2 mm) |
Class 2 Compacted Stranded Aluminium · Outer diameter 30.2 mm
Class 2 Compacted Stranded Aluminium · Outer diameter 35.6 mm
Class 2 Compacted Stranded Aluminium · Outer diameter 41.7 mm
Technical data
Sizes
Representative configurations from the series specification; select a row to prefill the quotation tool.
| Configuration | Conductor & shield | Insulation / wall | Outer sheath | Outer diameter mm | Min. bend radius mm | Max. conductor resistance @ 20 °C Ω/km | Conductor weight kg/km | Cable weight kg/km | Key electrical / optical rating | Part designation | Enquiry |
|---|---|---|---|---|---|---|---|---|---|---|---|
| EAXCG / EAXCWB / EAXCVB 0.6/1kV–8.7/15kV NBN | |||||||||||
| 1×150/25 mm² | Class 2 Compacted Stranded Aluminium | NBN HD 620 XLPE dielectric | LSZH Jacket | 30.2 | 453 | 0.19 | 571.9 | 1,505 | 250 A | EAXCG / EAXCWB / EAXCVB 0.6/1kV–8.7/15kV NBN (1×150/25 mm²) | |
| 1×185/25 mm² | Class 2 Compacted Stranded Aluminium | NBN HD 620 XLPE dielectric | LSZH Jacket | 35.6 | 534 | 0.15 | 796.1 | 2,095 | 286 A | EAXCG / EAXCWB / EAXCVB 0.6/1kV–8.7/15kV NBN (1×185/25 mm²) | |
| 1×240/25 mm² | Class 2 Compacted Stranded Aluminium | NBN HD 620 XLPE dielectric | LSZH Jacket | 41.7 | 626 | 0.12 | 1,089.1 | 2,866 | 336 A | EAXCG / EAXCWB / EAXCVB 0.6/1kV–8.7/15kV NBN (1×240/25 mm²) | |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Conductor resistance & continuity | Within maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228 | Every manufactured drum length |
| Dielectric withstand / spark test | No breakdown across insulation, screen or armour | Every manufactured drum length |
| Sample tests | ||
| Vertical flame propagation & jacket qualification | Self-extinguishing and compliant with reference standard limits | Type qualification & periodic lot audit |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.