Contact

EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV SynergridEAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV Synergrid manufactured to NBN HD 620-10C / Synergrid C2/112, rated 8.7/15 (17.5) kV – 12/20 (24) kV and -25°C to +90°C with a 15 × OD minimum bending radius for renewable energy installations.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
EMC screen
Oil-resistant
Approved
Order designation
EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV (1×240/35 mm²)
Outer diameter
35.8 mm
Cable weight
2,115 kg/km
Min. bend radius
537 mm
Conductor & shield
Class 2 Watertight Compacted Aluminium
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
8.7/15–12/20 kV
NBN HD 620-10C / Synergrid C2/112
Temperature
-25°C to +90°C
Fixed / flex duty
Min. bend radius
15 × OD
35.8–49.4 mm
Screening
Cu Tape Screen
Helical copper tape earth screen
Outer sheath
LSZH Jacket
Halogen-free fire-safety corridors
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per NBN HD 620-10C / Synergrid C2/112 (EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV) — confirmed in the datasheet and quotation for your order.

Application fit

Is EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.

Motor stator, traction & converter leads

Suitable

Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

TBM gantry & advancing tunnel reel

Suitable

Low-smoke zero-halogen outer sheath minimizes toxic acid gas emission and smoke obscuration in fire events.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use WXG / WXG-D MV Reeling Cable

Substation MV/HV underground duct bank

Suitable

High-dielectric 12/20 kV XLPE/LSZH construction feeds medium- and high-voltage substation duct banks, transformer bays, and utility feeders.

Typical machinesRenewable Energy & EV ChargingPower distribution & utility networksRailways, tunnels & public infrastructureProcess instrumentation & oil/gas skidsIndustrial automation & control cabinetsRenewable energy, marine & heavy industry

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
1Conductor1×240/35 mm² Watertight Al (e)
2Insulation & Core IdentificationSynergrid EAXeCeG XLPE dielectric (240 mm² Watertight Aluminium)
3Screen / Bedding / Armour LayerSemi-conductive longitudinal water-swellable tape (e) + Helical copper wire screen (35 mm²) + copper tape + Aluminium/PE radial water-blocking laminate barrier
4Outer Protective SheathRed HFFR / LSZH outer sheath (OD 35.8 mm)

1×240/35 mm²

Class 2 Watertight Compacted Aluminium · Outer diameter 35.8 mm

1×300/35 mm²

Class 2 Watertight Compacted Aluminium · Outer diameter 42.2 mm

1×400/35 mm²

Class 2 Watertight Compacted Aluminium · Outer diameter 49.4 mm

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per NBN HD 620-10C / Synergrid C2/112 (EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
8.7/15 (17.5) kV – 12/20 (24) kV
Conductor & core insulation
1×240/35 mm² Watertight Al (e) · Synergrid EAXeCeG XLPE dielectric (240 mm² Watertight Aluminium)
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
-25°C to +90°C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
NBN HD 620-10C / Synergrid C2/112

Mechanical

Minimum bending radius
15 × OD
Screening / armour architecture
Semi-conductive longitudinal water-swellable tape (e) + Helical copper wire screen (35 mm²) + copper tape + Aluminium/PE radial water-blocking laminate barrier
Outer sheath material & colour
Red HFFR / LSZH outer sheath (OD 35.8 mm)

Reference standards

Reference standard
NBN HD 620-10C / Synergrid C2/112
Hazardous Substance Compliance
CE, UKCA, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Conductor weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV
1×240/35 mm²Class 2 Watertight Compacted AluminiumSynergrid EAXeCeG XLPE dielectricLSZH Jacket35.85370.12803.72,115336 AEAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV (1×240/35 mm²)
1×300/35 mm²Class 2 Watertight Compacted AluminiumSynergrid EAXeCeG XLPE dielectricLSZH Jacket42.26330.091,119.12,945385 AEAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV (1×300/35 mm²)
1×400/35 mm²Class 2 Watertight Compacted AluminiumSynergrid EAXeCeG XLPE dielectricLSZH Jacket49.47410.071,530.34,027445 AEAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV (1×400/35 mm²)
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228Every manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation, screen or armourEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing and compliant with reference standard limitsType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

NBN HD 620-10C / Synergrid C2/112 CompliantEN 10204 3.1 Factory Test CertificateCE, UKCA, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

EAXECEG / EAXECWB / EAXECG 8.7/15KV–12/20KV SYNERGRID / TEBAOFLEX.COM — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
250 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-04
Updated
2026-11-04

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV designed for?
EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV is engineered for renewable energy installations under NBN HD 620-10C / Synergrid C2/112, operating over -25°C to +90°C with a minimum bending radius of 15 × OD.
How is EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV constructed across its layers?
Its 4-layer architecture combines 1×240/35 mm² Watertight Al (e) with Synergrid EAXeCeG XLPE dielectric (240 mm² Watertight Aluminium), Semi-conductive longitudinal water-swellable tape (e) + Helical copper wire screen (35 mm²) + copper tape + Aluminium/PE radial water-blocking laminate barrier and Red HFFR / LSZH outer sheath (OD 35.8 mm).
What standards and routine factory tests apply to EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV?
Every manufactured drum is tested to NBN HD 620-10C / Synergrid C2/112 for conductor continuity, dielectric voltage withstand and sheath integrity, supplied with an EN 10204 3.1 inspection certificate.
What sizes and drum lengths are available for EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV?
Representative sizes include 1×240/35 mm², 1×300/35 mm² and 1×400/35 mm², supplied on 250 m, 500 m or 1,000 m export drums or custom cut lengths.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

EAXeCeG / EAXeCWB / EAXeCG 8.7/15kV–12/20kV Synergrid

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote