0.6/1 kV Cu/PE/CTS/PE/DSTA/PVC-AT Armoured Substation Pilot CableIEC 60502-1 / BS EN 50288-7 · 0.6/1 kV · -25 °C to +70 °C industrial CU-PE-CTS-PE-DSTA-PVC-AT

0.6/1 kV Cu/PE/CTS/PE/DSTA/PVC-AT Anti-Termite Armoured Substation Pilot Cable (CU-PE-CTS-PE-DSTA-PVC-AT Pilot) engineered to IEC 60502-1 / BS EN 50288-7 for 0.6/1 kV service across -25 °C to +70 °C, featuring stranded copper conductor and pvc-at outer sheath

Approved
Low-EMC design
EMC screen
Outdoor & humid
Order designation
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G2.5
Outer Ø ≈
10.8 mm
Total weight ≈
186 kg/km
Min. bend R (fixed)
86 mm
Configuration
4 × 2.5 mm²
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
Per IEC 60502-1 / BS EN 50288-7
Operating temp.
−25…+70 °C
Continuous thermal rating
Min. bend radius
12 × OD
Installed / fixed routing
Conductor
copper conductor
High-conductivity copper conductor
Outer layer
PVC-AT outer
Extruded PVC-AT outer sheath
Standard
IEC 60502-1
IEC 60502-1 / BS EN 50288-7

Typical values for this cable type, based on IEC 60502-1 / BS EN 50288-7 — confirmed in the datasheet and quotation for your order.

Application fit

Is CU-PE-CTS-PE-DSTA-PVC-AT Pilot right for your machine?

0.6/1 kV Cu/PE/CTS/PE/DSTA/PVC-AT Anti-Termite Armoured Substation Pilot Cable (CU-PE-CTS-PE-DSTA-PVC-AT Pilot) engineered to IEC 60502-1 / BS EN 50288-7 for 0.6/1 kV service across -25 °C to +70 °C, featuring stranded copper conductor and pvc-at outer sheath

Fixed installation

Suitable

Engineered and verified for fixed service in accordance with IEC 60502-1 / BS EN 50288-7.

Switchgear & control cabinet wiring

Suitable

Suitable for switchgear, control panels and equipment terminations within 12 × OD bend radius.

TBM gantry & advancing tunnel reel

With conditions

Use mechanical conduit or armoured protection where exposed to rock fall or crushing loads.

Motorised monospiral reel

Not suitable

Not designed for high-speed monospiral crane reeling; select a dedicated reeling cable.

NSHTOU Reeling Cable
Typical machinesRenewable Energy & EV ChargingHigh-Voltage Grid & Substation InterconnectsWind, Solar & Hydro Power EvacuationUtility Overhead & Underground DistributionIndustrial Power InfrastructureRefinery & Petrochemical Process Units

Construction

Layer by layer

Shown: CU-PE-CTS-PE-DSTA-PVC-AT Pilot (IEC 60502-1 / BS EN 50288-7) with stranded copper conductor, pe core insulation and pvc-at outer sheath (8-layer construction).

12345678
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Stranded copper conductorHigh-conductivity copper conductor per IEC 60502-1 / BS EN 50288-7IEC 60502-1 / BS EN 50288-7
2PE core insulationExtruded PE dielectric (individual core / group layer)IEC 60502-1 / BS EN 50288-7
3PE binder tapeHelically applied pe binder tapeIEC 60502-1 / BS EN 50288-7
4Copper tape screenCopper tape screen metallic electromagnetic screen (lapped tape)IEC 60502-1 / BS EN 50288-7
5PE beddingExtruded PE bedding protective layer (continuous layer)IEC 60502-1 / BS EN 50288-7
6Inner steel armour tapeInner steel armour tape mechanical protection (lapped tape)IEC 60502-1 / BS EN 50288-7
7Outer steel armour tapeOuter steel armour tape mechanical protection (lapped tape)IEC 60502-1 / BS EN 50288-7
8PVC-AT outer sheathExtruded PVC-AT outer sheath protective layer (continuous layer)IEC 60502-1 / BS EN 50288-7

CU-PE-CTS-PE-DSTA-PVC-AT Pilot — Standard Execution

Built to IEC 60502-1 / BS EN 50288-7 with stranded copper conductor and pvc-at outer sheath

CU-PE-CTS-PE-DSTA-PVC-AT Pilot — Custom Cross-Sections

Full range of metric mm² and AWG/kcmil conductor sizes per IEC 60502-1 / BS EN 50288-7

CU-PE-CTS-PE-DSTA-PVC-AT Pilot — Export Drum Supply

Supplied with EN 10204 3.1 routine dielectric & conductor resistance test certificate

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on IEC 60502-1 / BS EN 50288-7. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / duty
0.6/1 kV (IEC 60502-1 / BS EN 50288-7)
Conductor construction
Stranded copper conductor — High-conductivity copper conductor per IEC 60502-1 / BS EN 50288-7
Primary insulation / dielectric
PE core insulation — Extruded PE dielectric (individual core / group layer)

Thermal

Continuous operating temperature
−25…+70 °C per IEC 60502-1 / BS EN 50288-7
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s adiabatic limit depending on dielectric class)
Minimum installation temperature
−5 °C (thermoplastic) / −25 °C (cross-linked or elastomer) / −40 °C (metallic)

Mechanical

Outer protection / covering
PVC-AT outer sheath — Extruded PVC-AT outer sheath protective layer (continuous layer)
Minimum bending radius
12 × OD (installed / static routing)
Layer count & geometry
8 concentric/structural layers verified by cross-section inspection

Resistance

Environmental & chemical durability
Engineered for industrial service in accordance with IEC 60502-1 / BS EN 50288-7
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing product standard
IEC 60502-1 / BS EN 50288-7
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
CU-PE-CTS-PE-DSTA-PVC-AT Pilot
Customs tariff (HS)
8544.49 / 8544.60 / 7614.10

Sizes

12 standard CU-PE-CTS-PE-DSTA-PVC-AT Pilot cable sizes

Manufactured to IEC 60502-1 / BS EN 50288-7 across standard single-core and multi-core cross-sections.

Dimensions, construction & weights
Order designationConfigurationOuter Ø ≈
mm
Weight ≈
kg/km
Min. bend R
fixed mm
Enquiry
CU-PE-CTS-PE-DSTA-PVC-AT Pilot Standard Production Schedule (0.6/1 kV · −25…+70 °C)
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 3G1.53 × 1.5 mm²8.410568
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G1.54 × 1.5 mm²9.212874
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 5G1.55 × 1.5 mm²10.115681
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 3G2.53 × 2.5 mm²9.814878
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G2.54 × 2.5 mm²10.818686
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 5G2.55 × 2.5 mm²11.922895
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G44 × 4.0 mm²12.6268101
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G64 × 6.0 mm²14.2365114
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G104 × 10 mm²17.5580140
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G164 × 16 mm²20.4845163
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G254 × 25 mm²24.81,290198
CU-PE-CTS-PE-DSTA-PVC-AT Pilot 4G354 × 35 mm²27.91,710223
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Single-core and multi-core sizes from 0.5 mm² up to 630 mm² (or AWG/kcmil) available per IEC 60502-1 / BS EN 50288-7.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor DC resistance & dimensional verification (IEC 60502-1 / BS EN 50288-7)DC resistance at 20 °C and geometry within IEC 60502-1 / BS EN 50288-7 class limitsEvery manufactured drum / spool
Routine dielectric / spark / structural integrity test (IEC 60502-1 / BS EN 50288-7)Zero breakdown or structural defect over full production lengthEvery manufactured drum / spool
Sample tests
Thermal aging, mechanical & material qualification (IEC 60502-1 / BS EN 50288-7)Full compliance with IEC 60502-1 / BS EN 50288-7 across −25…+70 °CType qualification & periodic sample audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

IEC 60502-1 CompliantEN 10204 3.1 Routine Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX CU-PE-CTS-PE-DSTA-PVC-AT Pilot <size> IEC 60502-1 0.6/1 kV CE
Delivery form
Non-returnable fumigated wooden drums or precision DIN spools
Standard lengths
500 m · 1000 m · 2000 m drums (custom cut lengths on request)
MOQ
500 m (stock sizes) · 1000 m (custom production)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-21
Updated
2026-10-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define CU-PE-CTS-PE-DSTA-PVC-AT Pilot (0.6/1 kV Cu/PE/CTS/PE/DSTA/PVC-AT Anti-Termite Armoured Substation Pilot Cable)?
CU-PE-CTS-PE-DSTA-PVC-AT Pilot (0.6/1 kV Cu/PE/CTS/PE/DSTA/PVC-AT Anti-Termite Armoured Substation Pilot Cable) is manufactured in accordance with IEC 60502-1 / BS EN 50288-7 for 0.6/1 kV service over -25 °C to +70 °C. Its 8-layer construction comprises stranded copper conductor, pe core insulation, pe binder tape, copper tape screen, pe bedding, inner steel armour tape, outer steel armour tape, pvc-at outer sheath.
What is the minimum bending radius and installation temperature for CU-PE-CTS-PE-DSTA-PVC-AT Pilot?
The minimum installed bending radius for CU-PE-CTS-PE-DSTA-PVC-AT Pilot is 12 × OD across its continuous operating temperature range of -25 °C to +70 °C, ensuring mechanical and dielectric stability without conductor or insulation strain.
How are the concentric layers of CU-PE-CTS-PE-DSTA-PVC-AT Pilot arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Stranded copper conductor (High-conductivity copper conductor per IEC 60502-1 / BS EN 50288-7); (02) PE core insulation (Extruded PE dielectric (individual core / group layer)); (03) PE binder tape (Helically applied pe binder tape); (04) Copper tape screen (Copper tape screen metallic electromagnetic screen (lapped tape)); (05) PE bedding (Extruded PE bedding protective layer (continuous layer)); (06) Inner steel armour tape (Inner steel armour tape mechanical protection (lapped tape)); (07) Outer steel armour tape (Outer steel armour tape mechanical protection (lapped tape)); (08) PVC-AT outer sheath (Extruded PVC-AT outer sheath protective layer (continuous layer)).
What factory test certificates are supplied with CU-PE-CTS-PE-DSTA-PVC-AT Pilot?
Every production drum or spool of CU-PE-CTS-PE-DSTA-PVC-AT Pilot undergoes routine conductor DC resistance, dimensional and dielectric/integrity testing per IEC 60502-1 / BS EN 50288-7, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for CU-PE-CTS-PE-DSTA-PVC-AT Pilot

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

0.6/1 kV Cu/PE/CTS/PE/DSTA/PVC-AT Armoured Substation Pilot Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote