Fixed installation
Durable 1000 V Cu-ETP geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Product
AC Laminated Cu-Foil Lead stacks dozens of precision-rolled 0.10–0.20 mm Cu-ETP bare copper foils into a compact flat flexible expansion connector for high-current generators, busducts, EV/BESS racks, and furnace transformers.
Typical values for this cable type, based on DIN 46433 · EN 13602 Cu-ETP · IEC 61439 (ref.) — confirmed in the datasheet and quotation for your order.
Application fit
AC Laminated Cu-Foil Lead stacks dozens of precision-rolled 0.10–0.20 mm Cu-ETP bare copper foils into a compact flat flexible expansion connector for high-current generators, busducts, EV/BESS racks, and furnace transformers.
Durable 1000 V Cu-ETP geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Compact 1000 V Cu-ETP profile routes cleanly inside dense switchgear enclosures, BESS racks, and high-current test benches.
High-capacity 1000 V Cu-ETP feeder connects motor control centers (MCC) cleanly to heavy plant machinery and main distribution panels.
High-current DC 1000 V Cu-ETP design links BESS battery modules, rack combiners, and power conversion cabinets safely.
1000 V Cu-ETP construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR1000 V Cu-ETP outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.
Use EMC-VFD Submersible EPDMConstruction
Representative construction of AC Laminated Cu-Foil Lead: IEC 60228 Class 6 extra-flexible bare annealed copper, Stacked uninsulated electrolytic bare copper laminations (Cu-ETP), and Uninsulated bare copper foil stack outer surface.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6 |
| 2 | Uninsulated outer weave / lay | Uninsulated bare copper foil stack outer surfaceDIN 46433 |
Uninsulated flexible bare copper construction for maximal natural air-cooling convection.
Technical data
Sizes
| Cross-section (W × H mm) | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 5×D mm |
|---|---|---|---|---|---|
| 1×50 mm² (25×2.0 mm) | 2.0 | 0.386 | 455 | 529 | 10.0 |
| 1×100 mm² (40×2.5 mm) | 2.5 | 0.192 | 910 | 1,052 | 12.0 |
| 1×150 mm² (50×3.0 mm) | 3.0 | 0.129 | 1,365 | 1,576 | 15.0 |
| 1×240 mm² (60×4.0 mm) | 4.0 | 0.080 | 2,184 | 2,518 | 20.0 |
| 1×400 mm² (80×5.0 mm) | 5.0 | 0.049 | 3,640 | 4,192 | 25.0 |
| 1×630 mm² (100×6.3 mm) | 6.3 | 0.029 | 5,733 | 6,599 | 32.0 |
| 1×1000 mm² (100×10.0 mm) | 10.0 | 0.019 | 9,100 | 10,471 | 50.0 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| High-voltage dielectric withstand test | 3 kV AC without breakdown | Every manufactured length |
| Continuity & conductor DC resistance | Per IEC 60228 Class 6 at 20 °C | Every drum / assembly |
| Sample tests | ||
| Tensile, dimensional & pressure check | Rated -60 °C to +150 °C continuous | Per production lot |
| Environmental, thermal & mechanical qualification | 0.10–0.20 mm Cu-ETP Foils · Press-Welded Terminal Ready | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.