Fixed installation
Durable 1000 V SiR geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Product
AC Fire-Protected HC encloses extra-flexible bare copper power ropes inside a thermal fibreglass braid coated with heavy red-oxide iron-oxide silicone rubber (pyro-barrier) to deflect molten splash and 500 °C radiant heat.
Typical values for this cable type, based on IEC 60228 Class 6 · DIN VDE 0250 (ref.) · IEC 60331 (ref.) — confirmed in the datasheet and quotation for your order.
Application fit
AC Fire-Protected HC encloses extra-flexible bare copper power ropes inside a thermal fibreglass braid coated with heavy red-oxide iron-oxide silicone rubber (pyro-barrier) to deflect molten splash and 500 °C radiant heat.
Durable 1000 V SiR geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Extra-flexible 1000 V SiR stranding and 8×D bend radius connect dynamic welding guns, drives, and furnace feeders.
Rugged 1000 V SiR construction handles stationary heavy-plant cable trenches, rolling-mill feeders, and industrial power bays.
Thermal-aged 1000 V SiR insulation maintains dielectric safety near industrial boilers, ovens, and high-ambient thermal equipment.
1000 V SiR construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR1000 V SiR outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.
Use EMC-VFD Submersible EPDMConstruction
Representative construction of AC Fire-Protected HC Cable: IEC 60228 Class 6 extra-flexible bare annealed copper, High-temperature silicone rubber + thermal fibreglass inner barrier, and Red-oxide iron-oxide silicone-coated fibreglass outer sheath (silicone/glass).
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6 |
| 2 | Cooling core / primary dielectric | High-temperature silicone rubber + thermal fibreglass inner barrierIEC 60228 Class 6 |
| 3 | Outer sheath / hose | Red-oxide iron-oxide silicone-coated fibreglass outer sheath (silicone/glass)Molten-Metal Splash Barrier |
Single-core high-duty construction protected by Red-oxide iron-oxide silicone-coated fibreglass outer sheath (silicone/glass).
Technical data
Sizes
| Cross-section mm² | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 8×D mm |
|---|---|---|---|---|---|
| 1×120 mm² | 24.3 | 0.161 | 1,152 | 1,904 | 194 |
| 1×150 mm² | 26.1 | 0.129 | 1,440 | 2,344 | 209 |
| 1×185 mm² | 28.0 | 0.106 | 1,776 | 2,854 | 224 |
| 1×240 mm² | 30.7 | 0.080 | 2,304 | 3,654 | 246 |
| 1×300 mm² | 33.2 | 0.064 | 2,880 | 4,518 | 266 |
| 1×400 mm² | 37.0 | 0.049 | 3,840 | 5,959 | 296 |
| 1×500 mm² | 40.3 | 0.038 | 4,800 | 7,392 | 322 |
| 1×630 mm² | 44.1 | 0.029 | 6,048 | 9,247 | 353 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| High-voltage dielectric withstand test | 4 kV AC without breakdown | Every manufactured length |
| Continuity & conductor DC resistance | Per IEC 60228 Class 6 at 20 °C | Every drum / assembly |
| Sample tests | ||
| Tensile, dimensional & pressure check | Rated -50 °C to +500 °C continuous | Per production lot |
| Environmental, thermal & mechanical qualification | Molten-Metal Splash Barrier · 500 °C Short-Term Radiant | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.