Contact

AC Bare Copper Flexible Rope 120–700 mm² Uninsulated LeadUninsulated extra-flexible Class 6 bare copper rope for busbars & earthing

AC Bare Cu Rope 120–700 is a 7×7 extra-flexible uninsulated electrolytic bare copper rope conductor designed for maximum natural air-cooling convection on transformer expansion joints, furnace shunts, and heavy earthing.

Oil-resistant
Flame-retardant
Approved
Order designation
AC Bare-Cu Rope 120-700 1×300 mm²
Outer Ø
24.2 mm
Max. R20
0.064 Ω/km
Weight
3,318 kg/km
Min. bend R
145 mm
All sizes (8)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
1000 V
Test voltage 3 kV AC
Temp. (fixed)
-60°C…+150°C
Flexing: -60 °C to +150 °C
Construction
Bare Cu-ETP
Uninsulated 7×7 rope-lay
Min. bend radius
6 × OD
High-current flexible routing
Conductor
Bare Cu · Cl.6
Per DIN 46438
Size range
1×120–1×700
8 standard configurations

Typical values for this cable type, based on DIN 46438 · IEC 60228 Class 6 · EN 13602 Cu-ETP — confirmed in the datasheet and quotation for your order.

Application fit

Is AC Bare-Cu Rope 120-700 right for your machine?

AC Bare Cu Rope 120–700 is a 7×7 extra-flexible uninsulated electrolytic bare copper rope conductor designed for maximum natural air-cooling convection on transformer expansion joints, furnace shunts, and heavy earthing.

Fixed installation

Suitable

Durable 1000 V Cu-ETP geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.

Switchgear & control cabinet wiring

Suitable

Compact 1000 V Cu-ETP profile routes cleanly inside dense switchgear enclosures, BESS racks, and high-current test benches.

Cable trench & heavy drive bay

Suitable

Rugged 1000 V Cu-ETP construction handles stationary heavy-plant cable trenches, rolling-mill feeders, and industrial power bays.

Welding power source & electrode lead

Suitable

Extra-flexible heat- and spatter-resistant 1000 V Cu-ETP build delivers low-drop current to welding tongs and shop floor leads.

Energy chain / drag chain

Not suitable

1000 V Cu-ETP construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.

Use (N)12YRDC11Y-J/O PUR

Immersion & wet locations

Not suitable

1000 V Cu-ETP outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.

Use EMC-VFD Submersible EPDM
Typical machinesPower transformers, switchgear & busduct jointsResistance welding guns & heavy fabrication shopsBESS battery racks, EV test benches & rectifiersSteel mills, foundries & high-current power bays

Construction

Layer by layer

Representative construction of AC Bare-Cu Rope 120-700: IEC 60228 Class 6 extra-flexible bare annealed copper, Uninsulated 7×7 rope-lay electrolytic bare copper (air-insulated), and Uninsulated bare electrolytic copper rope outer lay.

12
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1ConductorIEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6
2Uninsulated outer weave / layUninsulated bare electrolytic copper rope outer layDIN 46438

AC Bare-Cu Rope 120-700 Uninsulated

Uninsulated flexible bare copper construction for maximal natural air-cooling convection.

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on DIN 46438 · IEC 60228 Class 6 · EN 13602 Cu-ETP. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage
1000 V
Test voltage
3 kV AC
Conductor
Bare Cu · Cl.6
Core / dielectric
Uninsulated 7×7 rope-lay electrolytic
Impedance / insulation
≥ 1,000 MΩ·km at 20 °C

Thermal

Temp. range (fixed)
-60 °C to +150 °C
Temp. range (flexing)
-60 °C to +150 °C
Peak / short-circuit
+160 °C (5 s)
Min. bending radius
6 × OD

Resistance

Primary performance
99.95% Electrolytic Cu-ETP
Environment / duty
Max Air Convection Cooling
Mechanical / special
Ultra-Flex Rope-Lay
Outer finish
Uninsulated bare electrolytic copper rope

Sizes

Air-Cooled High-Current Sizes (mm²)
Cross-section
mm²
Outer Ø ≈
mm
Max. R20
Ω/km
Copper index
kg/km
Weight ≈
kg/km
Min. bend R
6×D mm
1×120 mm²15.30.1611,1521,33192
1×150 mm²17.10.1291,4401,662103
1×185 mm²19.00.1061,7762,048114
1×240 mm²21.70.0802,3042,656130
1×300 mm²24.20.0642,8803,318145
1×400 mm²28.00.0493,8404,422168
1×500 mm²31.30.0384,8005,526188
1×700 mm²37.00.0276,7207,734222
  • Conductor DC resistance R20 at 20 °C per IEC 60228 Class 6.
  • Minimum bending radius calculated at 6 × nominal outer diameter (OD). Custom terminations available on request.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
High-voltage dielectric withstand test3 kV AC without breakdownEvery manufactured length
Continuity & conductor DC resistancePer IEC 60228 Class 6 at 20 °CEvery drum / assembly
Sample tests
Tensile, dimensional & pressure checkRated -60 °C to +150 °C continuousPer production lot
Environmental, thermal & mechanical qualification99.95% Electrolytic Cu-ETP · Max Air Convection CoolingType approval

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

DIN 46438IEC 60228 Class 6EN 13602 Cu-ETPEN 10204 3.1 Factory Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

AC Bare-Cu Rope 120-700 1000 V TEBAOFLEX.COM [DIN 46438] [Size] [Metre mark]
Delivery form
Custom assemblies, coils or export drums
Standard lengths
Cut-to-length · 100 m · 500 m · 1,000 m
MOQ
1 assembly / 50 m (stock) · 300 m (custom)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-23
Updated
2026-11-23

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What makes AC Bare-Cu Rope 120-700 suited for demanding 1000 V installations?
AC Bare-Cu Rope 120-700 combines IEC 60228 Class 6 extra-flexible bare annealed copper with Uninsulated 7×7 rope-lay electrolytic bare copper (air-insulated) and Uninsulated bare electrolytic copper rope outer lay. Uninsulated bare Cu-ETP rope maximizes heat dissipation and accommodates thermal busbar expansion.
What minimum bending radius should be respected for AC Bare-Cu Rope 120-700?
Maintain a minimum bending radius of 6 × OD across -60 °C to +150 °C flexing temperatures to ensure long mechanical and dielectric service life.
Can AC Bare-Cu Rope 120-700 be delivered pre-terminated with custom lugs, water fittings, or subsea connectors?
Yes. TEBAOFLEX supplies AC Bare-Cu Rope 120-700 either in bulk lengths or factory-assembled with copper lugs, water-cooled swivel fittings, or molded subsea wet-mate connectors.
What quality tests and certificates accompany every shipment of AC Bare-Cu Rope 120-700?
AC Bare-Cu Rope 120-700 conforms to DIN 46438, IEC 60228 Class 6, EN 13602 Cu-ETP (99.95% Electrolytic Cu-ETP) and ships with an EN 10204 3.1 routine factory test certificate.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for AC Bare-Cu Rope 120-700

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

AC Bare-Cu Rope 120-700 AC Bare Copper Flexible Rope 120–700 mm² Uninsulated Lead

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp