Fixed installation
Durable 1000 V Cu-ETP geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Product
AC Bare Cu Braid Shunt weaves ultra-fine 0.15–0.20 mm Cu-ETP bare copper wires into a flat, uninsulated tubular/flat braid for switchgear expansion joints, breaker links, transformer shunts, and vibration-decoupled earth straps.
Typical values for this cable type, based on DIN 46444 · EN 13602 Cu-ETP · IEC 60228 (ref.) — confirmed in the datasheet and quotation for your order.
Application fit
AC Bare Cu Braid Shunt weaves ultra-fine 0.15–0.20 mm Cu-ETP bare copper wires into a flat, uninsulated tubular/flat braid for switchgear expansion joints, breaker links, transformer shunts, and vibration-decoupled earth straps.
Durable 1000 V Cu-ETP geometry installs cleanly along transformer links, busbar transitions, trays, and industrial bays.
Compact 1000 V Cu-ETP profile routes cleanly inside dense switchgear enclosures, BESS racks, and high-current test benches.
Compact flame-retardant 1000 V Cu-ETP geometry routes neatly through dense switchgear ducts, control cabinets, and DIN-rail terminals.
Rugged 1000 V Cu-ETP construction handles stationary heavy-plant cable trenches, rolling-mill feeders, and industrial power bays.
1000 V Cu-ETP construction is built for stationary or light-flex runs, not continuous high-cycle drag-chain flexing.
Use (N)12YRDC11Y-J/O PUR1000 V Cu-ETP outer sheath is not AD8-rated for permanent water submersion; specify a submersible EPDM or water-blocked cable.
Use EMC-VFD Submersible EPDMConstruction
Representative construction of AC Bare-Cu Braid Shunt: IEC 60228 Class 6 extra-flexible bare annealed copper, Uninsulated flat-rolled woven electrolytic bare copper wire braid, and Uninsulated bare electrolytic copper flat braided surface.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Conductor | IEC 60228 Class 6 extra-flexible bare annealed copperIEC 60228 Class 6 |
| 2 | Uninsulated outer weave / lay | Uninsulated bare electrolytic copper flat braided surfaceDIN 46444 |
Uninsulated flexible bare copper construction for maximal natural air-cooling convection.
Technical data
Sizes
| Cross-section (W × H mm) | Outer Ø ≈ mm | Max. R20 Ω/km | Copper index kg/km | Weight ≈ kg/km | Min. bend R 5×D mm |
|---|---|---|---|---|---|
| 1×10 mm² (12×1.5 mm) | 1.5 | 1.910 | 91 | 111 | 7.5 |
| 1×16 mm² (16×1.8 mm) | 1.8 | 1.210 | 146 | 174 | 9.0 |
| 1×25 mm² (22×2.0 mm) | 2.0 | 0.780 | 228 | 268 | 10.0 |
| 1×35 mm² (25×2.5 mm) | 2.5 | 0.554 | 318 | 372 | 12.0 |
| 1×50 mm² (30×3.0 mm) | 3.0 | 0.386 | 455 | 529 | 15.0 |
| 1×70 mm² (35×3.5 mm) | 3.5 | 0.272 | 637 | 739 | 18.0 |
| 1×95 mm² (40×4.2 mm) | 4.2 | 0.206 | 864 | 1,000 | 21.0 |
| 1×120 mm² (45×4.8 mm) | 4.8 | 0.161 | 1,092 | 1,262 | 24.0 |
| 1×185 mm² (55×6.0 mm) | 6.0 | 0.106 | 1,684 | 1,943 | 30.0 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| High-voltage dielectric withstand test | 3 kV AC without breakdown | Every manufactured length |
| Continuity & conductor DC resistance | Per IEC 60228 Class 6 at 20 °C | Every drum / assembly |
| Sample tests | ||
| Tensile, dimensional & pressure check | Rated -60 °C to +150 °C continuous | Per production lot |
| Environmental, thermal & mechanical qualification | Flat Woven Cu-ETP Braid · Vibration & Expansion Proof | Type approval |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.