UL GTO-15 15 kVAC Silicone/PVC High-Voltage Gas-Tube-Sign WireUL 814 / CSA C22.2 No. 17 · 15 kVAC · -40 °C to +105 °C industrial GTO CABLE 15kVAC

UL GTO-15 15 kVAC Silicone/PVC High-Voltage Gas-Tube-Sign & Ignition Cable engineered to UL 814 / CSA C22.2 No. 17 for 15 kVAC service across -40 °C to +105 °C, featuring stranded tinned copper conductor and pvc outer sheath with minimum bending radius 8 × OD.

Approved
Oil-resistant
Outdoor & humid
Ozone, UV & moisture
Order designation
GTO CABLE 15kVAC 4G2.5
Outer Ø ≈
10.8 mm
Total weight ≈
186 kg/km
Min. bend R (fixed)
86 mm
Configuration
4 × 2.5 mm²
All sizes (12)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
15 kVAC
Per UL 814 / CSA C22.2 No. 17
Operating temp.
−40…+105 °C
Continuous thermal rating (UL 814)
Min. bend radius
8 × OD
Installed / fixed routing
Conductor
tinned copper
High-conductivity tinned copper
Outer layer
PVC outer sheath
Extruded PVC outer sheath protective
Standard
UL 814
UL 814 / CSA C22.2 No. 17

Typical values for this cable type, based on UL 814 / CSA C22.2 No. 17 — confirmed in the datasheet and quotation for your order.

Application fit

Is GTO-15 (15 kVAC) right for your machine?

UL GTO-15 15 kVAC Silicone/PVC High-Voltage Gas-Tube-Sign & Ignition Cable engineered to UL 814 / CSA C22.2 No. 17 for 15 kVAC service across -40 °C to +105 °C, featuring stranded tinned copper conductor and pvc outer sheath with minimum bending radius 8 × OD.

Furnace, kiln & high-temp zone

Suitable

Engineered and verified for furnace kiln service in accordance with UL 814 / CSA C22.2 No. 17.

Switchgear & control cabinet wiring

Suitable

Engineered and verified for cabinet chassis service in accordance with UL 814 / CSA C22.2 No. 17.

Fixed installation

Suitable

Qualified for fixed installation on trays, racks, conduits or supports per UL 814 / CSA C22.2 No. 17.

TBM gantry & advancing tunnel reel

With conditions

Use mechanical conduit or armoured protection where exposed to rock fall or crushing loads.

Typical machinesMetallurgical, Glass & Ceramic FurnacesHigh-Temperature Thermal ProcessingHeavy Industrial Kilns & OvensPower Generation & Petrochemical HeatersAutomated Assembly & Packaging Lines

Construction

Layer by layer

Shown: GTO CABLE 15kVAC (UL 814 / CSA C22.2 No. 17) with stranded tinned copper conductor, silicone rubber insulation and pvc outer sheath (3-layer construction).

123
Schematic, not to scale — generated from the layer data
#LayerMaterial & reference
1Stranded tinned copper conductorHigh-conductivity tinned copper conductor per UL 814 / CSA C22.2 No. 17UL 814 / CSA C22.2 No. 17
2Silicone rubber insulationExtruded Silicone rubber insulation dielectric (continuous layer)UL 814 / CSA C22.2 No. 17
3PVC outer sheathExtruded PVC outer sheath protective layer (continuous layer)UL 814 / CSA C22.2 No. 17

GTO CABLE 15kVAC — Standard Execution

Built to UL 814 / CSA C22.2 No. 17 with stranded tinned copper conductor and pvc outer sheath

GTO CABLE 15kVAC — Custom Cross-Sections

Full range of metric mm² and AWG/kcmil conductor sizes per UL 814 / CSA C22.2 No. 17

GTO CABLE 15kVAC — Export Drum Supply

Supplied with EN 10204 3.1 routine dielectric & conductor resistance test certificate

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on UL 814 / CSA C22.2 No. 17. Values for your order are confirmed in the datasheet and quotation.

Electrical

Rated voltage / duty
15 kVAC (UL 814 / CSA C22.2 No. 17)
Conductor construction
Stranded tinned copper conductor — High-conductivity tinned copper conductor per UL 814 / CSA C22.2 No. 17
Primary insulation / dielectric
Silicone rubber insulation — Extruded Silicone rubber insulation dielectric (continuous layer)

Thermal

Continuous operating temperature
−40…+105 °C per UL 814 / CSA C22.2 No. 17
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s adiabatic limit depending on dielectric class)
Minimum installation temperature
−5 °C (thermoplastic) / −25 °C (cross-linked or elastomer) / −40 °C (metallic)

Mechanical

Outer protection / covering
PVC outer sheath — Extruded PVC outer sheath protective layer (continuous layer)
Minimum bending radius
8 × OD (installed / static routing)
Layer count & geometry
3 concentric/structural layers verified by cross-section inspection

Resistance

Environmental & chemical durability
Engineered for industrial service in accordance with UL 814 / CSA C22.2 No. 17
RoHS & REACH compliance
RoHS 2 (2011/65/EU + 2015/863) & REACH SVHC compliant

Reference standards

Governing product standard
UL 814 / CSA C22.2 No. 17
Quality management & inspection
ISO 9001:2015 & EN 10204 3.1 factory routine inspection

Identification

Model designation
GTO CABLE 15kVAC
Customs tariff (HS)
8544.49 / 8544.60 / 7614.10

Sizes

12 standard GTO CABLE 15kVAC cable sizes

Manufactured to UL 814 / CSA C22.2 No. 17 across standard single-core and multi-core cross-sections.

Dimensions, construction & weights
Order designationConfigurationOuter Ø ≈
mm
Weight ≈
kg/km
Min. bend R
fixed mm
Enquiry
GTO CABLE 15kVAC Standard Production Schedule (15 kVAC · −40…+105 °C)
GTO CABLE 15kVAC 3G1.53 × 1.5 mm²8.410568
GTO CABLE 15kVAC 4G1.54 × 1.5 mm²9.212874
GTO CABLE 15kVAC 5G1.55 × 1.5 mm²10.115681
GTO CABLE 15kVAC 3G2.53 × 2.5 mm²9.814878
GTO CABLE 15kVAC 4G2.54 × 2.5 mm²10.818686
GTO CABLE 15kVAC 5G2.55 × 2.5 mm²11.922895
GTO CABLE 15kVAC 4G44 × 4.0 mm²12.6268101
GTO CABLE 15kVAC 4G64 × 6.0 mm²14.2365114
GTO CABLE 15kVAC 4G104 × 10 mm²17.5580140
GTO CABLE 15kVAC 4G164 × 16 mm²20.4845163
GTO CABLE 15kVAC 4G254 × 25 mm²24.81,290198
GTO CABLE 15kVAC 4G354 × 35 mm²27.91,710223
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Single-core and multi-core sizes from 0.5 mm² up to 630 mm² (or AWG/kcmil) available per UL 814 / CSA C22.2 No. 17.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor DC resistance & dimensional verification (UL 814 / CSA C22.2 No. 17)DC resistance at 20 °C and geometry within UL 814 / CSA C22.2 No. 17 class limitsEvery manufactured drum / spool
Routine dielectric / spark / structural integrity test (UL 814 / CSA C22.2 No. 17)Zero breakdown or structural defect over full production lengthEvery manufactured drum / spool
Sample tests
Thermal aging, mechanical & material qualification (UL 814 / CSA C22.2 No. 17)Full compliance with UL 814 / CSA C22.2 No. 17 across −40…+105 °CType qualification & periodic sample audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

UL 814 CompliantEN 10204 3.1 Routine Test CertificateCE, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

TEBAOFLEX GTO CABLE 15kVAC <size> UL 814 15 kVAC CE
Delivery form
Non-returnable fumigated wooden drums or precision DIN spools
Standard lengths
500 m · 1000 m · 2000 m drums (custom cut lengths on request)
MOQ
500 m (stock sizes) · 1000 m (custom production)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-10-21
Updated
2026-10-21

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What governing standard and construction define GTO CABLE 15kVAC (UL GTO-15 15 kVAC Silicone/PVC High-Voltage Gas-Tube-Sign & Ignition Cable)?
GTO CABLE 15kVAC (UL GTO-15 15 kVAC Silicone/PVC High-Voltage Gas-Tube-Sign & Ignition Cable) is manufactured in accordance with UL 814 / CSA C22.2 No. 17 for 15 kVAC service over -40 °C to +105 °C. Its 3-layer construction comprises stranded tinned copper conductor, silicone rubber insulation, pvc outer sheath.
What is the minimum bending radius and installation temperature for GTO CABLE 15kVAC?
The minimum installed bending radius for GTO CABLE 15kVAC is 8 × OD across its continuous operating temperature range of -40 °C to +105 °C, ensuring mechanical and dielectric stability without conductor or insulation strain.
How are the concentric layers of GTO CABLE 15kVAC arranged from inside to outside?
From inside to outside, the construction sequence is: (01) Stranded tinned copper conductor (High-conductivity tinned copper conductor per UL 814 / CSA C22.2 No. 17); (02) Silicone rubber insulation (Extruded Silicone rubber insulation dielectric (continuous layer)); (03) PVC outer sheath (Extruded PVC outer sheath protective layer (continuous layer)).
What factory test certificates are supplied with GTO CABLE 15kVAC?
Every production drum or spool of GTO CABLE 15kVAC undergoes routine conductor DC resistance, dimensional and dielectric/integrity testing per UL 814 / CSA C22.2 No. 17, and is delivered with an EN 10204 3.1 factory test certificate.

Request a quote

Get an engineering quote for GTO-15 (15 kVAC)

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

UL GTO-15 15 kVAC Silicone/PVC High-Voltage Gas-Tube-Sign Wire

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 