Furnace, kiln & high-temp zone
Designed for warm-zone junction boxes, drying ovens, foundry luminaires, and heating apparatus up to +110 °C continuous.
Product
Harmonised H07G-U solid-conductor heat-resistant single-core wire to EN 50525-2-42, combining a Class 1 tinned copper core with halogen-free cross-linked EVA (EI3) insulation for fixed internal wiring up to +110 °C.
Typical values for this cable type, based on EN 50525-2-42 / DIN VDE 0285-525-2-42 — confirmed in the datasheet and quotation for your order.
Application fit
Select H07G-U where a rigid, form-holding solid core (Class 1) is required for permanent internal wiring of luminaires, heating appliances, switchgear, and industrial ovens up to +110 °C.
Designed for warm-zone junction boxes, drying ovens, foundry luminaires, and heating apparatus up to +110 °C continuous.
Solid Class 1 tinned copper core holds its formed bend geometry cleanly inside control panels, busbar chambers, and push-in terminals.
Approved for fixed installation in dry or damp rooms inside surface or embedded conduits and closed installation ducts.
Solid Class 1 conductor and single-layer EVA insulation are exclusively for static routing; never use on reels or moving drives.
Use H07G-K for flexible leadsConstruction
Single-core solid construction per EN 50525-2-42 (DIN VDE 0285-525-2-42): Class 1 tinned copper conductor and halogen-free cross-linked EVA compound EI3.
| # | Layer | Material & reference |
|---|---|---|
| 1 | Solid tinned copper conductor | Tinned annealed electrolytic copper wire (Cu-ETP1, IEC 60228 Class 1)Tin barrier prevents copper catalysed thermal ageing of the elastomer at +110 °C |
| 2 | Primary EVA dielectric | Cross-linked ethylene-vinyl acetate (EVA) elastomer compound Type EI3Thermoset network resists melting, solder-iron contact, and thermal deformation |
| 3 | Integral halogen-free outer skin | Homogeneous extruded EI3 EVA surface (colour-coded)Halogen-free per IEC 60754-1/2 and flame-retardant per IEC 60332-1-2 |
Harmonised EN 50525-2-42 solid Class 1 sizes in black, blue, brown, red, white, and green-yellow
Extended 300/500 V solid EVA hook-up gauges for compact luminaire ballasts and thermostat blocks
Technical data
Sizes
Engineering dimensions, conductor stranding, mass and electrical ratings for H07G-U per EN 50525-2-42 / DIN VDE 0285-525-2-42.
| Order designation | Cross-section / size | Conductor build | Wall ≈ mm | Outer Ø ≈ mm | Metal kg/km | Weight ≈ kg/km | Min. bend R fixed mm | Enquiry |
|---|---|---|---|---|---|---|---|---|
| Standard H07G-U configurations | ||||||||
| H07G-U 1×0.5 | 0.5 | 1×0.80 mm solid | 0.60 | 2.00 | 4.8 | 8.6 | 8 | |
| H07G-U 1×0.75 | 0.75 | 1×0.98 mm solid | 0.60 | 2.20 | 7.2 | 11.6 | 9 | |
| H07G-U 1×1 | 1 | 1×1.13 mm solid | 0.60 | 2.40 | 9.6 | 14.7 | 10 | |
| H07G-U 1×1.5 | 1.5 | 1×1.38 mm solid | 0.80 | 3.00 | 14.4 | 22.4 | 12 | |
| H07G-U 1×2.5 | 2.5 | 1×1.78 mm solid | 0.90 | 3.60 | 24.0 | 35.0 | 14 | |
| H07G-U 1×4 | 4 | 1×2.26 mm solid | 1.00 | 4.30 | 38.4 | 53.4 | 17 | |
| H07G-U 1×6 | 6 | 1×2.76 mm solid | 1.00 | 4.80 | 57.6 | 74.8 | 19 | |
| H07G-U 1×10 | 10 | 1×3.57 mm solid | 1.20 | 6.00 | 96.0 | 121.9 | 24 | |
| H07G-U 1×16 | 16 | 1×4.51 mm solid | 1.20 | 7.00 | 153.6 | 185.3 | 28 | |
| Configuration | Max. DC R @ 20 °C Ω/km | Primary rating (A or kV) | Derated / AC rating | Dielectric test V AC rms |
|---|---|---|---|---|
| 1×0.5 mm² | 36.70 | 12.0 | 9.0 | 2,500 |
| 1×0.75 mm² | 24.80 | 16.0 | 12.0 | 2,500 |
| 1×1 mm² | 18.20 | 20.0 | 15.0 | 2,500 |
| 1×1.5 mm² | 12.20 | 26.0 | 20.0 | 2,500 |
| 1×2.5 mm² | 7.56 | 36.0 | 28.0 | 2,500 |
| 1×4 mm² | 4.70 | 49.0 | 37.0 | 2,500 |
| 1×6 mm² | 3.11 | 63.0 | 48.0 | 2,500 |
| 1×10 mm² | 1.84 | 86.0 | 66.0 | 2,500 |
| 1×16 mm² | 1.16 | 115.0 | 88.0 | 2,500 |
Quality & approvals
Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.
| Testing & inspection | Test value / reference | Frequency |
|---|---|---|
| Routine tests | ||
| Dielectric spark / high-voltage withstand test | 100 % in-line spark and AC/DC dielectric withstand per EN 50525-2-42 / DIN VDE 0285-525-2-42 | Every manufactured length |
| Conductor DC resistance & continuity check | Within maximum 20 °C resistance limit specified for H07G-U | Every spool or drum length |
| Sample tests | ||
| Thermal ageing & dimensional verification | Wall thickness, concentricity and post-ageing elongation per EN 50525-2-42 / DIN VDE 0285-525-2-42 | Per production batch |
| Flame, outgassing or high-temperature endurance | Qualified to EN 50525-2-42 / DIN VDE 0285-525-2-42 thermal and environmental performance criteria | Type qualification |
Marking & supply
Sheath marking
Technical documents
FAQ
Not covered here? Send your drawing — an engineer replies within 2 business hours.
Request a quote
Your selection and application details are copied into the enquiry form below.
Use + Add next to a size or configuration.
Add your operating conditions here to include them in your enquiry.