Contact

AL/HEPR/PO HXM1 0.6/1kV Wind Tower CableAL/HEPR/PO HXM1 0.6/1kV Wind Tower Cable manufactured to IEC 60502-1 / EN 50363, rated 0.6/1 kV and -40°C to +90°C with a 12 × OD minimum bending radius for infrastructure & construction installations.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
Oil-resistant
Approved
Order designation
AL/HEPR/PO HXM1 0.6/1kV Wind Tower (3×150 mm²)
Outer diameter
44.0 mm
Cable weight
3,194 kg/km
Min. bend radius
528 mm
Conductor & shield
Class 2 Compacted Stranded Aluminium
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
IEC 60502-1 / EN 50363
Temperature
-40°C to +90°C
Fixed / flex duty
Min. bend radius
12 × OD
44.0–60.7 mm
Screening
Unshielded
Fixed / flex duty
Outer sheath
LSZH Jacket
Halogen-free fire-safety corridors
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per IEC 60502-1 / EN 50363 (AL/HEPR/PO HXM1 0.6/1kV Wind Tower) — confirmed in the datasheet and quotation for your order.

Application fit

Is AL/HEPR/PO HXM1 0.6/1kV Wind Tower right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.

Motor stator, traction & converter leads

Suitable

Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

TBM gantry & advancing tunnel reel

Suitable

Low-smoke zero-halogen outer sheath minimizes toxic acid gas emission and smoke obscuration in fire events.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use TRA 0.6/1 kV PUR Reeling Cable

Wind turbine tower & nacelle

Suitable

Cold-flex and torsion-tested 0.6/1 kV HEPR construction supports wind turbine tower risers, yaw loops, and nacelle switchgear.

Typical machinesBuilding & Fire SafetyPower distribution & utility networksRailways, tunnels & public infrastructureProcess instrumentation & oil/gas skidsIndustrial automation & control cabinetsRenewable energy, marine & heavy industry

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

AL/HEPR/PO HXM1 0.6/1kV Wind Tower – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
1Conductor3×150 mm² Class 2 Stranded Aluminium
2Insulation & Core IdentificationHEPR (Hard Ethylene Propylene Rubber) 90°C insulation (150 mm² Class 2 Al)
3Screen / Bedding / Armour LayerHalogen-free compound inner filling
4Outer Protective SheathBlack HXM1 Low Smoke Zero Halogen Polyolefin (PO) outer sheath (OD 44.0 mm)

3×150 mm²

Class 2 Compacted Stranded Aluminium · Outer diameter 44.0 mm

3×185 mm²

Class 2 Compacted Stranded Aluminium · Outer diameter 51.9 mm

3×240 mm²

Class 2 Compacted Stranded Aluminium · Outer diameter 60.7 mm

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per IEC 60502-1 / EN 50363 (AL/HEPR/PO HXM1 0.6/1kV Wind Tower). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
0.6/1 kV
Conductor & core insulation
3×150 mm² Class 2 Stranded Aluminium · HEPR (Hard Ethylene Propylene Rubber) 90°C insulation (150 mm² Class 2 Al)
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
-40°C to +90°C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
IEC 60502-1 / EN 50363

Mechanical

Minimum bending radius
12 × OD
Screening / armour architecture
Halogen-free compound inner filling
Outer sheath material & colour
Black HXM1 Low Smoke Zero Halogen Polyolefin (PO) outer sheath (OD 44.0 mm)

Reference standards

Reference standard
IEC 60502-1 / EN 50363
Hazardous Substance Compliance
CE, UKCA, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Conductor weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
AL/HEPR/PO HXM1 0.6/1kV Wind Tower
3×150 mm²Class 2 Compacted Stranded AluminiumHEPR 90°C insulationLSZH Jacket44.05280.191,213.73,194250 AAL/HEPR/PO HXM1 0.6/1kV Wind Tower (3×150 mm²)
3×185 mm²Class 2 Compacted Stranded AluminiumHEPR 90°C insulationLSZH Jacket51.96230.151,690.24,448286 AAL/HEPR/PO HXM1 0.6/1kV Wind Tower (3×185 mm²)
3×240 mm²Class 2 Compacted Stranded AluminiumHEPR 90°C insulationLSZH Jacket60.77280.122,311.56,083336 AAL/HEPR/PO HXM1 0.6/1kV Wind Tower (3×240 mm²)
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228Every manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation, screen or armourEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing and compliant with reference standard limitsType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

IEC 60502-1 / EN 50363 CompliantEN 10204 3.1 Factory Test CertificateCE, UKCA, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

AL/HEPR/PO HXM1 0.6/1KV WIND TOWER CABLE / TEBAOFLEX.COM — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
250 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-04
Updated
2026-11-04

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is AL/HEPR/PO HXM1 0.6/1kV Wind Tower designed for?
AL/HEPR/PO HXM1 0.6/1kV Wind Tower is engineered for infrastructure & construction installations under IEC 60502-1 / EN 50363, operating over -40°C to +90°C with a minimum bending radius of 12 × OD.
How is AL/HEPR/PO HXM1 0.6/1kV Wind Tower constructed across its layers?
Its 4-layer architecture combines 3×150 mm² Class 2 Stranded Aluminium with HEPR (Hard Ethylene Propylene Rubber) 90°C insulation (150 mm² Class 2 Al), Halogen-free compound inner filling and Black HXM1 Low Smoke Zero Halogen Polyolefin (PO) outer sheath (OD 44.0 mm).
What standards and routine factory tests apply to AL/HEPR/PO HXM1 0.6/1kV Wind Tower?
Every manufactured drum is tested to IEC 60502-1 / EN 50363 for conductor continuity, dielectric voltage withstand and sheath integrity, supplied with an EN 10204 3.1 inspection certificate.
What sizes and drum lengths are available for AL/HEPR/PO HXM1 0.6/1kV Wind Tower?
Representative sizes include 3×150 mm², 3×185 mm² and 3×240 mm², supplied on 250 m, 500 m or 1,000 m export drums or custom cut lengths.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for AL/HEPR/PO HXM1 0.6/1kV Wind Tower

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

AL/HEPR/PO HXM1 0.6/1kV Wind Tower Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote