Contact

N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 Portuguese LV CableN1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 Portuguese LV Cable manufactured to IEC 60502-1 / DMA-C33-200, rated 0.6/1 kV and -25°C to +90°C with a 12 × OD minimum bending radius for infrastructure & construction installations.

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Flame-retardant
Outdoor & humid
Approved
Order designation
N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 (5G10 mm²)
Outer diameter
18.8 mm
Cable weight
831 kg/km
Min. bend radius
226 mm
Conductor & shield
Class 2 Stranded Plain Copper
All sizes (3)
Engineering reply in 2 business hoursCut-to-length export drumsEN 10204 3.1 certificate per drum
Rated voltage
0.6/1 kV
IEC 60502-1 / DMA-C33-200
Temperature
-25°C to +90°C
Fixed / flex duty
Min. bend radius
12 × OD
18.8–25.9 mm
Screening
Unshielded
Fixed / flex duty
Outer sheath
Outdoor PE
UV-stabilized moisture-barrier PE
Core / size range
3 sizes
3 standard configurations

Typical values for this cable type, based on Reference specification per IEC 60502-1 / DMA-C33-200 (N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356) — confirmed in the datasheet and quotation for your order.

Application fit

Is N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 right for your machine?

Engineered for industrial installations requiring verified electrical, mechanical and environmental performance.

Fixed installation

Suitable

Approved for cable tray, duct, direct burial or clipped fixed installations per applicable wiring regulations.

Motor stator, traction & converter leads

Suitable

Flexible stranded conductors withstand equipment vibration, mobile hook-ups and routine flexing.

Energy chain / drag chain

With conditions

Fixed or moderate-flex construction; for continuous high-acceleration drag chains, select a dedicated Class 6 chain cable.

Offshore platform & shipboard deck trays

Suitable

Outer sheath compound resists industrial oils, moisture ingress, abrasion and outdoor weathering.

Vertical / spreader reel

Not suitable

Not intended for high-tension crane spreader reeling drums; select a dedicated 2PNCT or 3PNCT reeling cable.

Use TRA 0.6/1 kV PUR Reeling Cable

Dual-tier power & PLC tray

Suitable

Screened 0.6/1 kV XLPE/PE construction suppresses electromagnetic interference on shared industrial power and PLC signal trays.

Typical machinesBuilding & Fire SafetyPower distribution & utility networksRailways, tunnels & public infrastructureProcess instrumentation & oil/gas skidsIndustrial automation & control cabinetsRenewable energy, marine & heavy industry

Construction

Layer by layer

Cross-section colours are aligned to the supplied product cutaway; layer dimensions follow the reference specification.

N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 – Layered cable cutaway
Layer cutaway
#LayerMaterial & reference
1Conductor5G10 mm² Class 2 Stranded Cu (RM)
2Insulation & Core IdentificationNP 2356 XLPE core insulation (10 mm² Class 2 Stranded Copper)
3Screen / Bedding / Armour LayerExtruded elastomeric/plastomeric inner sheath
4Outer Protective SheathBlack UV-resistant Polyethylene (PE) outer sheath with yellow stripe (OD 18.8 mm)

5G10 mm²

Class 2 Stranded Plain Copper · Outer diameter 18.8 mm

5G16 mm²

Class 2 Stranded Plain Copper · Outer diameter 22.2 mm

5G25 mm²

Class 2 Stranded Plain Copper · Outer diameter 25.9 mm

Technical data

Ratings & operating limits

Typical values: Typical values for this cable type, based on Reference specification per IEC 60502-1 / DMA-C33-200 (N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356). Values for your order are confirmed in the datasheet and quotation.

Electrical

Nominal / reference voltage
0.6/1 kV
Conductor & core insulation
5G10 mm² Class 2 Stranded Cu (RM) · NP 2356 XLPE core insulation (10 mm² Class 2 Stranded Copper)
Routine dielectric / continuity test
100% factory drum spark & continuity verified

Thermal

Operating temperature range
-25°C to +90°C
Short-circuit / peak thermal limit
+160 °C to +250 °C (5 s conductor thermal limit)
Flame & fire performance
IEC 60502-1 / DMA-C33-200

Mechanical

Minimum bending radius
12 × OD
Screening / armour architecture
Extruded elastomeric/plastomeric inner sheath
Outer sheath material & colour
Black UV-resistant Polyethylene (PE) outer sheath with yellow stripe (OD 18.8 mm)

Reference standards

Reference standard
IEC 60502-1 / DMA-C33-200
Hazardous Substance Compliance
CE, UKCA, RoHS 2 (2011/65/EU) & REACH SVHC compliant
Quality & Batch Traceability
EN 10204 3.1 Factory Inspection Certificate

Sizes

Sizes & engineering data

Representative configurations from the series specification; select a row to prefill the quotation tool.

All sizes
ConfigurationConductor & shieldInsulation / wallOuter sheathOuter diameter
mm
Min. bend radius
mm
Max. conductor resistance @ 20 °C
Ω/km
Copper weight
kg/km
Cable weight
kg/km
Key electrical / optical ratingPart designationEnquiry
N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356
5G10 mm²Class 2 Stranded Plain CopperNP 2356 XLPE core insulationOutdoor PE18.82261.81432.183160 AN1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 (5G10 mm²)
5G16 mm²Class 2 Stranded Plain CopperNP 2356 XLPE core insulationOutdoor PE22.22661.13601.61,15780 AN1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 (5G16 mm²)
5G25 mm²Class 2 Stranded Plain CopperNP 2356 XLPE core insulationOutdoor PE25.93110.72822.61,582106 AN1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 (5G25 mm²)
  • Typical values for this cable type; dimensions and weights for your order are confirmed in the quotation.
  • Dimensions and weights are nominal manufacturing targets subject to standard production tolerances.

Quality & approvals

Testing & inspection

Routine tests on every production length, sample and type tests per batch — documented on an EN 10204 3.1 inspection certificate.

  1. ConductorClass 5 stranding
  2. Spark test100 % in-line
  3. Lay-upCores, earth, fillers
  4. SheathingInner, braid / screen, outer
  5. Electrical testsAC voltage, resistance
  6. DimensionsOD, wall thickness
  7. Inspection documents & dispatchDrum & dispatch
Testing & inspectionTest value / referenceFrequency
Routine tests
Conductor resistance & continuityWithin maximum Ω/km limit at 20 °C per IEC 60228 / BS EN 60228Every manufactured drum length
Dielectric withstand / spark testNo breakdown across insulation, screen or armourEvery manufactured drum length
Sample tests
Vertical flame propagation & jacket qualificationSelf-extinguishing and compliant with reference standard limitsType qualification & periodic lot audit

Inspection certificate

Issued with every drum, listing the routine test results for that length.

Product approvals

IEC 60502-1 / DMA-C33-200 CompliantEN 10204 3.1 Factory Test CertificateCE, UKCA, RoHS 2 (2011/65/EU) & REACH

Company certificates

ISO 9001ISO 14001ISO 45001VDE marks approvalUL / cULCE · LVD / EMC

Marking & supply

Ordering & delivery

Sheath marking

N1XE-R / N1XE-U / N1XV 0.6/1KV NP 2356 PORTUGUESE LV CABLE / TEBAOFLEX.COM — sequential metre marking
Delivery form
Heavy-duty export fumigated wooden drums or steel reels with moisture-sealed ends
Standard lengths
250 m, 500 m, 1000 m continuous drum lengths or custom cut-to-length runs
MOQ
100 m (standard configurations) · 300 m (custom builds)
Lead time
2–4 weeks ex-works
Incoterms
EXW, FCA, FOB, CIF, DAP

Technical documents

Downloads

Revision
2026-11-04
Updated
2026-11-04

FAQ

Questions engineers ask first

Not covered here? Send your drawing — an engineer replies within 2 business hours.

What applications is N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 designed for?
N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 is engineered for infrastructure & construction installations under IEC 60502-1 / DMA-C33-200, operating over -25°C to +90°C with a minimum bending radius of 12 × OD.
How is N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 constructed across its layers?
Its 4-layer architecture combines 5G10 mm² Class 2 Stranded Cu (RM) with NP 2356 XLPE core insulation (10 mm² Class 2 Stranded Copper), Extruded elastomeric/plastomeric inner sheath and Black UV-resistant Polyethylene (PE) outer sheath with yellow stripe (OD 18.8 mm).
What standards and routine factory tests apply to N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356?
Every manufactured drum is tested to IEC 60502-1 / DMA-C33-200 for conductor continuity, dielectric voltage withstand and sheath integrity, supplied with an EN 10204 3.1 inspection certificate.
What sizes and drum lengths are available for N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356?
Representative sizes include 5G10 mm², 5G16 mm² and 5G25 mm², supplied on 250 m, 500 m or 1,000 m export drums or custom cut lengths.
Which technical documents are available?
Reference files are provided for project screening. Final parameters and the applicable document package are confirmed during quotation.

Request a quote

Get an engineering quote for N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356

Your selection and application details are copied into the enquiry form below.

01Selected sizes

Use + Add next to a size or configuration.

02Reel & motion

Add your operating conditions here to include them in your enquiry.

03Message for our engineers

N1XE-R / N1XE-U / N1XV 0.6/1kV NP 2356 Portuguese LV Cable

Selected sizes:


Reel & motion:
- Reel type: 
- Drum core diameter (mm): 
- Cable length on drum (m): 
- Travel speed (m/min): 
- Max. acceleration: 
- Cycles per hour: 
- Length and quantity: 
- Ambient temperature: 
- Exposure (outdoor, water, oil, abrasion): 
- Destination country: 
- Equipment and operating conditions: 
Send via WhatsApp

DatasheetRequest a quote