EN 50288-7 SWA armé XLPE/LSZH câbleBS EN 50288-7+90 °C XLPE / SWA / LSZHIEC 60754 & 61034

RE-2X(st)H SWAH Armé Instrumentation Câble+90 °C XLPE/LSZH galvanisé acier fil armé sans halogène instrumentation câble

+90 °C XLPE/LSZH galvanisé acier fil armé sans halogène instrumentation câble

Conception faible CEM
Écran CEM
Ignifuge
Extérieur et humide
Désignation de commande
RE-2X(st)H PiMF SWAH 4×2×1.5
Ø ext. ≈
19.9 mm
Cuivre masse
129 kg/km
Total masse ≈
735 kg/km
Min. courbure R (fixe)
199 mm
Toutes les dimensions (17)
Réponse technique sous 2 heures ouvréesTourets d’exportation coupés à la longueurCertificat EN 10204 3.1 par touret
Tension assignée
300/500 V
EN 50288-7 · 2000 V AC essai
Armouring
Galvanisé SWA
EN 10257-1 rond acier fils
Température
−40…+90 °C
XLPE conducteur · +250 °C court-circuit
LSZH caractéristique assignée
IEC 60754/61034
sans halogène · ≥ 60 % léger trans.
Max.. L/R ratio
≤ 25 / 40 µH/Ω
0.5–1.0 mm² (25) · 1.5 mm² (40)
Rayon de courbure
10 × OD
fixe acheminement · 12 × OD traction

Valeurs types pour ce type de câble, basés sur BS EN 50288-7 / EN 10257-1 / IEC 60754 — confirmées dans la fiche technique et le devis de votre commande.

Applications

RE-2X(st)H SWAH convient-il à votre machine ?

Sans halogène 300/500 V armé procédé instrumentation câble built à BS EN 50288-7 avec Class 2 conducteurs en cuivre, +90 °C XLPE (2X) isolation, collectif ou PiMF Al/ PET écran, LSZH Bourrage intérieur, galvanisé acier fil armure (SWA) et LSZH gaine extérieure.

Portique de tunnelier TBM et avancement

Adapté

Galvanisé acier fil armure (SWA) sur extrudé LSZH Bourrage intérieur permet direct burial et culvert acheminement.

Chemins de câbles offshore et navires

Adapté

UV -stabilised LSZH gaine extérieure et SWA armure withstand harsh ouvert-air petrochemical environments.

Installation fixe

Adapté

Routes directly d'extérieur trenches en indoor sans halogène DCS marshalling rooms sans transition coffrets.

Machines typesLNG Liquefaction & Regasification TerminalsPetrochemical & Hydrogen Procédé UnitésSouterrain Utility Tunnels & Metro InfrastructurePuissance Génération & FGD Environmental SystèmesCommande Building Direct Trench Entries

Construction

Couche par couche

Illustré: RE-2X(st)H PiMF SWAH 4×2×1.5 mm² avec Class 2 cuivre paires, +90 °C XLPE isolation, PiMF + collectif Al/ PET écrans, extrudé LSZH bourrage, 1.25 mm galvanisé acier fil armure et LSZH gaine extérieure.

123456
Schéma sans échelle — généré à partir des données des couches
#CoucheMatériau et référence
1Toronné conducteurs en cuivreRecuit cuivre nu ou étamé, à 7 fils toronné (IEC 60228 Class 2)Faible DC boucle résistance pour champ transmetteurs et RTDs
2Polyéthylène réticulé (XLPE / 2X)Thermodurcissable XLPE selon EN 50290-2-29 (+90 °C continu, +250 °C court-circuit)Faible mutuel capacitance (≤ 100–115 nF/km) et élevé thermique stabilité
3Individuel & collectif Al/ PET écransAl/ PET laminated ruban + 0.5 mm² cuivre étamé drain fil (OS ou PiMF+OS)100 % électrostatique interférence réjection
4Extrudé LSZH Bourrage intérieur (H)Sans halogène ignifuge polyoléfine mélange extrudé sur le collectif écranAssure un circulaire étanche aux gaz seat pour Ex-d / Ex-e presse-étoupe intérieur seals sans PVC halogens
5Galvanisé acier fil armure (SWA)Unique couche de rond galvanisé acier fils (0.9 / 1.25 / 1.6 mm selon EN 10257-1)Élevé écrasement, choc, rongeurs et traction-tension mécanique résistance
6Faible émission de fumée Sans halogène gaine extérieure (H)Sans halogène ignifuge polyoléfine (LTS1 / HM4), Noir RAL 9005 ou Bleu RAL 5015 (Ex-i)IEC 60332-3-22/24, IEC 60754-1/2 & IEC 61034-2 compliant

RE-2X(st)H SWAH (OS + SWA)

+90 °C XLPE paires/triads avec collectif écran, LSZH bourrage, SWA et LSZH gaine extérieure

RE-2X(st)H PiMF SWAH

Individuellement et Blindé collectivement paires (PiMF) avec LSZH bourrage, SWA et LSZH gaine

Données techniques

Valeurs nominales et limites de service

Valeurs types: Valeurs types pour ce type de câble, basés sur BS EN 50288-7 / EN 10257-1 / IEC 60754. Les valeurs de votre commande sont confirmées dans la fiche technique et le devis.

Électriques

Tension assignée U0/U
300/500 V
Tension d'essai
2000 V AC (conducteur/conducteur & conducteur/écran) pour 1 min
Résistance d'isolement
≥ 5000 MΩ·km à +20 °C
Mutuel capacitance (à 800 Hz)
≤ 100 nF/km (OS) · ≤ 115 nF/km (PiMF)
Max.. L/R ratio
≤ 25 µH/Ω (0.5–1.0 mm²) · ≤ 40 µH/Ω (1.5 mm²)

Thermiques

Operating température, fixe
−40 °C à +90 °C
Operating température, installation
−5 °C à +50 °C
Court-circuit conducteur température
+250 °C (max. 5 s)

Mécaniques

Armure fil diamètre
0.90 mm / 1.25 mm / 1.60 mm galvanisé acier (EN 10257-1)
Rayon minimal de courbure, fixe
10 × OD
Rayon de courbure minimal, pendant traction
12 × OD

Résistance

Non-propagation de la flamme
IEC 60332-1-2 & IEC 60332-3-22/24 (Cat. un/C)
Halogène acid gaz
IEC 60754-1 (0 % halogène) · IEC 60754-2 (pH ≥ 4.3, ≤ 10 µS/mm)
Fumée density
IEC 61034-2 léger transmittance ≥ 60 %

Normes de référence

Conception & armure standards
BS EN 50288-7 & BS EN 10257-1
Norme du conducteur
IEC 60228 Class 2
Dangereux section conformité
IEC 60079-14 (Ex-i, Ex-e, Ex-d)

Identification

Repérage des conducteurs
Noir / Blanc numérotés 1, 2… (Triads: Noir/Wh/Rd)
Couleur de la gaine extérieure
Noir (RAL 9005) ou Bleu (RAL 5015 Ex-i)
Code tarifaire douanier (HS)
8544.49

Dimensions

17 standard RE-2X(st)H SWAH armé LSZH instrumentation sections

+90 °C XLPE Isolation de conducteur, LSZH Bourrage intérieur, galvanisé SWA et LSZH gaine extérieure.

Dimensions, SWA fil section & weights
Désignation de commandeFormatSWA fil ØØ ext. ≈
mm
Cuivre
kg/km
Masse ≈
kg/km
Min. courbure R
fixe mm
Demande
0.5 mm² SWA Armé XLPE/LSZH — L/R ≤ 25 µH/Ω
RE-2X(st)H SWAH 1×2×0.51×2×0.5 mm²0.9 mm SWA10.615218106
RE-2X(st)H SWAH 2×2×0.52×2×0.5 mm²0.9 mm SWA13.025305130
RE-2X(st)H PiMF SWAH 4×2×0.54×2×0.5 mm²0.9 mm SWA15.552428155
RE-2X(st)H PiMF SWAH 8×2×0.58×2×0.5 mm²1.25 mm SWA19.598685195
RE-2X(st)H PiMF SWAH 12×2×0.512×2×0.5 mm²1.25 mm SWA22.4144885224
0.75 mm² SWA Armé XLPE/LSZH — L/R ≤ 25 µH/Ω
RE-2X(st)H SWAH 1×2×0.751×2×0.75 mm²0.9 mm SWA11.020240110
RE-2X(st)H SWAH 2×2×0.752×2×0.75 mm²0.9 mm SWA13.834346138
RE-2X(st)H PiMF SWAH 4×2×0.754×2×0.75 mm²0.9 mm SWA16.771490167
RE-2X(st)H PiMF SWAH 8×2×0.758×2×0.75 mm²1.25 mm SWA21.1136788211
1.0 mm² SWA Armé XLPE/LSZH — L/R ≤ 25 µH/Ω
RE-2X(st)H SWAH 1×2×1.01×2×1.0 mm²0.9 mm SWA11.425260114
RE-2X(st)H PiMF SWAH 4×2×1.04×2×1.0 mm²1.25 mm SWA18.190605181
RE-2X(st)H PiMF SWAH 8×2×1.08×2×1.0 mm²1.25 mm SWA22.5174905225
1.5 mm² SWA Armé XLPE/LSZH — L/R ≤ 40 µH/Ω
RE-2X(st)H SWAH 1×2×1.51×2×1.5 mm²0.9 mm SWA12.235300122
RE-2X(st)H SWAH 2×2×1.52×2×1.5 mm²0.9 mm SWA15.963455159
RE-2X(st)H PiMF SWAH 4×2×1.54×2×1.5 mm²1.25 mm SWA19.9129735199
RE-2X(st)H PiMF SWAH 8×2×1.58×2×1.5 mm²1.6 mm SWA25.22521,155252
RE-2X(st)H PiMF SWAH 12×2×1.512×2×1.5 mm²1.6 mm SWA29.03741,510290
  • Valeurs types pour ce type de câble ; les dimensions et masses de votre commande sont confirmées dans le devis.
  • À la fois le Bourrage intérieur et gaine extérieure sont 100 % sans halogène LSZH compounds.

Qualité et homologations

Essais et contrôle

Essais individuels sur chaque longueur produite, essais sur prélèvements et de type par lot — documentés sur un certificat EN 10204 3.1.

  1. ConducteurToronnage classe 5
  2. Essai à l’étincelle100 % en ligne
  3. AssemblageConducteurs, terre, bourrages
  4. GainageIntérieure, tresse / écran, extérieure
  5. Essais électriquesTension CA, résistance
  6. DimensionsDE, épaisseur de paroi
  7. Documents de contrôle et expéditionTouret et expédition
Essais et contrôleValeur d’essai / référenceFréquence
Essais individuels
2000 V AC diélectrique essai & mutuel capacitance contrôle2.0 kV AC pour 1 min; C ≤ 100 / 115 nF/kmChaque fabriqué tambour
Essais sur prélèvements
IEC 60754-1/2 & IEC 61034-2 LSZH verification sur bourrage et gaine< 0.5 % HCl; pH ≥ 4.3; ≥ 60 % léger transmittanceSelon LSZH batch
EN 10257-1 galvanisé acier fil armure inspectionFil diamètre, à la traction résistance et zinc coat masseSelon armure lot

Certificat de contrôle

Délivré avec chaque touret, indiquant les résultats des essais individuels pour cette longueur.

Homologations du produit

BS EN 50288-7 & EN 10257-1 CompliantIEC 60754-1/2 & IEC 61034-2 LSZHIEC 60332-1-2 & IEC 60332-3-22/24

Certificats de l’entreprise

ISO 9001ISO 14001ISO 45001Homologation VDEUL / cULCE · LVD / EMC

Marquage et livraison

Commande et livraison

Marquage de la gaine

TEBAOFLEX RE-2X(st)H SWAH <size> 300/500V EN 50288-7 SWA LSZH CE
Conditionnement de livraison
Non-returnable fumigated wooden tambours
Standard pas
500 m · 1000 m standard tambours (coupure pas sur demande)
Commande minimale
500 m (stock sections) · 1000 m (sur mesure)
Délai de livraison
2–4 weeks ex-travaille
Incoterms
EXW, FCA, FOB, CIF, DAP

Documents techniques

Téléchargements

Révision
2026-10-20
Mise à jour
2026-10-20

FAQ

Les premières questions des ingénieurs

Une autre question ? Envoyez votre plan — un ingénieur répond sous 2 heures ouvrées.

Why must à la fois le Bourrage intérieur ('H') et gaine extérieure ('H') be LSZH dans RE-2X(st)H SWAH?
Some manufacturers substitute un PVC Bourrage intérieur sous le acier fil armure tout en uniquement making le gaine extérieure LSZH . Dans un incendie, un PVC Bourrage intérieur still releases toxic hydrochloric acid gaz jusqu'à le armure interstices. RE-2X(st)H SWAH uses 100 % sans halogène LSZH compounds pour à la fois le Bourrage intérieur et gaine extérieure.
CAN RE-2X(st)H SWAH parcours directly d'extérieur burial trenches en indoor commande rooms?
Yes. Because it combine galvanisé acier fil armure (pour extérieur burial et pipe-rack écrasement résistance) avec IEC 60332-3-22/24 et IEC 60754/61034 LSZH incendie performance, it élimine le need pour extérieur-à-indoor marshalling transition junction coffrets à le commande building paroi.
What does le alternative code RE-2X(st)HRH mean?
RE-2X(st)HRH est le exact même câble sous VDE -Style lettering, où 'H' est le LSZH Bourrage intérieur, 'R' est le rond galvanisé acier fil armure, et le final 'H' est le LSZH gaine extérieure.
How should le écran et drain fil de RE-2X(st)H SWAH be earthed dans instrumentation et Ex-i boucles?
À empêcher circulating 50/60 Hz terre-boucle courants de coupling en millivolt ou 4–20 mA signaux, le Al/ PET écran et cuivre étamé drain fil de RE-2X(st)H SWAH should be lié à le propre instrumentation terre bar à un extrémité uniquement (typically dans le commande/marshalling cabinet) et isolé contre chassis contact à le champ transmitter ou junction coffret, dans accordance avec IEC 60079-14 et EN 50288-7 .

Demander un devis

Obtenez un devis technique pour RE-2X(st)H SWAH

Votre sélection et les détails de l’application sont copiés dans le formulaire ci-dessous.

01Dimensions sélectionnées

Utilisez + Ajouter à côté d’une dimension ou configuration.

02Enrouleur et mouvement

Ajoutez ici vos conditions de service pour les inclure dans votre demande.

03Message pour nos ingénieurs

RE-2X(st)H SWAH Armé Instrumentation Câble

Dimensions sélectionnées:


Enrouleur et mouvement:
- Type d’enrouleur: 
- Diamètre du noyau du tambour (mm): 
- Longueur de câble sur tambour (m): 
- Vitesse de déplacement (m/min): 
- Accélération maximale: 
- Cycles par heure: 
- Longueur et quantité: 
- Température ambiante: 
- Exposition (extérieur, eau, huile, abrasion): 
- Pays de destination: 
- Équipement et conditions de service: 
Envoyer par WhatsApp

Fiche techniqueDemander un devis