IEC 60584-3 Type JX thermocouple câbleIEC 60584-3 / ANSI MC96.1Fe (+) / CuNi (−) Véritable JXClass 1 (±1.5 °C) · ~52 µV/°C

JX / Type J extension Thermocouple CâbleVéritable Fe / CuNi (Type J) Class 1 & Class 2 thermocouple extension câble

Véritable Fe / CuNi (Type J) Class 1 & Class 2 thermocouple extension câble

Conception faible CEM
Écran CEM
Ignifuge
Résistant à l’huile
Désignation de commande
JX-PVC-PiMF 4×2×1.0
Ø ext. ≈
12.8 mm
Total masse ≈
208 kg/km
Min. courbure R (fixe)
96 mm
Configuration
4×2×1.0 mm² (7/0.43)
Toutes les dimensions (16)
Réponse technique sous 2 heures ouvréesTourets d’exportation coupés à la longueurCertificat EN 10204 3.1 par touret
Alliage paire
Fe (+) / CuNi
Pur Iron (+) / 55Cu45Ni (−)
EMF tolerance
Class 1: ±1.5 °C
±85 µV · Class 2: ±2.5 °C
Boucle résistance
≈ 0.59 Ω/m/paire
à 1.0 mm² (0.10 + 0.49 Ω/m)
IEC code couleur
+ Noir / − Wh
Noir gaine extérieure (ou Ex-i Bleu)
ANSI code couleur
+ Blanc / − Rouge
Noir gaine extérieure (ASTM E230)
Junction temp..
−25…+200 °C
véritable JX alliage EMF calibration

Valeurs types pour ce type de câble, basés sur IEC 60584-3 / ANSI MC96.1 / ASTM E230 — confirmées dans la fiche technique et le devis de votre commande.

Applications

JX / Type J extension convient-il à votre machine ?

De précision Type JX thermocouple extension câble built à IEC 60584-3 et ANSI MC96.1 avec véritable Iron (+ Fe) et Cuivre-Nickel (− CuNi) conducteurs, Class 1 (±1.5 °C) EMF tolerance, Al/ PET écran et PVC, XLPE/LSZH, FEP/PTFE ou SWA construction.

Installation fixe

Adapté

Supplied dans non armé PVC, XLPE/LSZH et +200 °C FEP/PTFE pour machines, chemins de câbles et marshalling cabinets.

Portique de tunnelier TBM et avancement

Adapté

SWA armé exécution (JX-XLPE-SWA / JX-PVC-SWA) assure complet direct-burial et écrasement protection.

Chemins de câbles offshore et navires

Adapté

Humidité-serré gaine extérieure empêche oxydation/rusting du positive Iron (+ Fe) conducteur.

Machines typesPlastics Extrusion & Injection MouldingCaoutchouc Vulcanisation & Tyre PressesReducing & Inert-Atmosphere FurnacesRefinery & Chemical Procédé HeatingPackaging & Food Processing Machines

Construction

Couche par couche

Illustré: JX-PVC -PiMF 4×2×1.0 mm² (IEC 60584-3) avec à 7 fils toronné Fe (+) et CuNi (−) conducteurs, Noir (+) / Blanc (−) numérotés isolation, individuel & collectif Al/ PET écrans et Noir RAL 9005 gaine extérieure.

12345
Schéma sans échelle — généré à partir des données des couches
#CoucheMatériau et référence
1Véritable Type JX thermocouple alliage conducteursPositive (+): Thermocouple-qualité Iron (Fe, strongly magnetic) · Negative (−): Cuivre-Nickel (CuNi 55/45, non-magnetic), massif ou à 7 fils toronnéMatches le ~52.6 µV/°C Seebeck slope de Type J sensors sur −25 °C à +200 °C
2Repérés par couleurs Isolation de conducteur105 °C HR-PVC, +90 °C XLPE, ou +200/+260 °C FEP/PTFE (IEC: + Noir / − Blanc; ANSI: + Blanc / − Rouge)Protège le Iron positive conducteur contre humidité et galvanic oxydation
3Individuel & collectif Al/ PET écransAluminium/ PET laminated ruban + 0.5 mm² cuivre étamé drain fil (OS ou PiMF+OS)Élimine élément chauffant-band SCR commutation noise
4En option SWA ou acier/cuivre tresse métalliqueNon armé, galvanisé tresse en fils d'acier (SY) pour extruder barrels, ou SWA pour souterrain trenchesTailored mécanique protection
5Gaine extérieure (Noir RAL 9005 ou Ex-i Bleu)Ignifuge PVC, Faible émission de fumée Sans halogène (LSZH), ou fluoropolymère FEP/PTFEIEC 60332-1-2 / IEC 60332-3-24 ignifuge

JX — IEC 60584-3 (Noir/Blanc)

Positive (+) Noir, Negative (−) Blanc, Gaine extérieure Noir (ou Bleu pour Ex-i)

JX — ANSI MC96.1 (Blanc/Rouge)

Positive (+) Blanc, Negative (−) Rouge, Gaine extérieure Noir selon ASTM E230

JX-FEP / JX-SWA

+200 °C FEP fluoropolymère pour hot extruder zones ou SWA armé pour extérieur trenches

Données techniques

Valeurs nominales et limites de service

Valeurs types: Valeurs types pour ce type de câble, basés sur IEC 60584-3 / ANSI MC96.1 / ASTM E230. Les valeurs de votre commande sont confirmées dans la fiche technique et le devis.

Électriques

Positive conducteur (+)
Thermocouple-qualité Iron (Fe, strongly magnetic, ~10 µΩ·cm)
Negative conducteur (−)
Cuivre-Nickel (CuNi ~55 % Cu / 45 % Ni, non-magnetic, ~49 µΩ·cm)
Tolerance Class 1 (IEC 60584-3)
±1.5 °C (±85 µV) sur −25 °C à +200 °C junction gamme
Tolerance Class 2 (IEC 60584-3)
±2.5 °C (±140 µV) sur −25 °C à +200 °C junction gamme
Nominal Seebeck coefficient
≈ 52.6 µV/°C (0 à +100 °C) · boucle R ≈ 0.59 Ω/m à 1.0 mm²

Thermiques

Thermoelectric calibration gamme
−25 °C à +200 °C (véritable extension qualité JX)
Isolation caractéristique assignée (par gaine Type)
−25…+105 °C (HR-PVC) · −40…+90 °C (XLPE/LSZH) · −60…+200 °C (FEP)

Mécaniques

Toronnage du conducteur
0.5 mm² (7/0.30) · 1.0 mm² (7/0.43) · 1.5 mm² (7/0.53) ou massif
Rayon minimal de courbure
7.5 × OD (non armé) · 10 × OD (SWA armé)

Résistance

Non-propagation de la flamme
IEC 60332-1-2 & IEC 60332-3-24 Cat. C
Humidité & huile protection
Hermetic extrudé Isolation de conducteur empêche Iron (+ Fe) rusting

Normes de référence

Thermocouple câble standard
IEC 60584-3, ANSI/ISA MC96.1 (ASTM E230) & DIN 43722
Câble construction standard
BS EN 50288-7 / BS 5308

Identification

IEC 60584-3 code couleur
(+) Noir · (−) Blanc · Gaine extérieure: Noir (ou Bleu Ex-i)
ANSI MC96.1 code couleur
(+) Blanc · (−) Rouge · Gaine extérieure: Noir
Code tarifaire douanier (HS)
8544.49

Dimensions

16 standard JX / Type J extension thermocouple câble sections

Disponible dans 1 à 24 paires dans PVC, XLPE/LSZH, FEP (+200 °C) et SWA armé constructions.

Dimensions, construction & weights
Désignation de commandeConfigurationIsolation / GaineTemp.. gammeØ ext. ≈
mm
Masse ≈
kg/km
Min. courbure R
fixe mm
Demande
JX Résistant à la chaleur PVC / PVC Blindé (−25…+105 °C)
JX-PVC-OS 1×2×0.51×2×0.5 mm² (7/0.30)PVC / PVC (OS)−25…+105 °C5.64342
JX-PVC-PiMF 2×2×0.52×2×0.5 mm² (7/0.30)PVC / PVC (PiMF+OS)−25…+105 °C8.68264
JX-PVC-PiMF 4×2×0.54×2×0.5 mm² (7/0.30)PVC / PVC (PiMF+OS)−25…+105 °C10.813981
JX-PVC-PiMF 8×2×0.58×2×0.5 mm² (7/0.30)PVC / PVC (PiMF+OS)−25…+105 °C14.1242106
JX-PVC-PiMF 12×2×0.512×2×0.5 mm² (7/0.30)PVC / PVC (PiMF+OS)−25…+105 °C16.9342127
JX-PVC-OS 1×2×1.01×2×1.0 mm² (7/0.43)PVC / PVC (OS)−25…+105 °C6.76650
JX-PVC-PiMF 4×2×1.04×2×1.0 mm² (7/0.43)PVC / PVC (PiMF+OS)−25…+105 °C12.820896
JX-PVC-OS 1×2×1.51×2×1.5 mm² (7/0.53)PVC / PVC (OS)−25…+105 °C7.59056
JX-PVC-PiMF 4×2×1.54×2×1.5 mm² (7/0.53)PVC / PVC (PiMF+OS)−25…+105 °C14.3280107
JX-PVC-PiMF 12×2×1.512×2×1.5 mm² (7/0.53)PVC / PVC (PiMF+OS)−25…+105 °C22.6698170
JX Haute température FEP / FEP Blindé (−60…+200 °C)
JX-FEP-OS 1×2×0.51×2×0.5 mm² (7/0.30)FEP / FEP (OS)−60…+200 °C4.63734
JX-FEP-PiMF 4×2×0.54×2×0.5 mm² (7/0.30)FEP / FEP (PiMF+OS)−60…+200 °C9.212569
JX-FEP-OS 1×2×1.01×2×1.0 mm² (7/0.43)FEP / FEP (OS)−60…+200 °C5.65742
JX XLPE / LSZH / SWA Armé Direct-Burial (−40…+90 °C)
JX-XLPE-SWA 1×2×1.51×2×1.5 mm² (7/0.53)XLPE / SWA / LSZH−40…+90 °C12.1294121
JX-XLPE-SWA 4×2×1.54×2×1.5 mm² (7/0.53)XLPE / SWA / LSZH−40…+90 °C19.8738198
JX-XLPE-SWA 8×2×1.58×2×1.5 mm² (7/0.53)XLPE / SWA / LSZH−40…+90 °C25.01,168250
  • Valeurs types pour ce type de câble ; les dimensions et masses de votre commande sont confirmées dans le devis.
  • Spécifier 'IEC' (+ Noir / − Blanc) ou 'ANSI' (+ Blanc / − Rouge) couleur repérage lorsque ordering.

Qualité et homologations

Essais et contrôle

Essais individuels sur chaque longueur produite, essais sur prélèvements et de type par lot — documentés sur un certificat EN 10204 3.1.

  1. ConducteurToronnage classe 5
  2. Essai à l’étincelle100 % en ligne
  3. AssemblageConducteurs, terre, bourrages
  4. GainageIntérieure, tresse / écran, extérieure
  5. Essais électriquesTension CA, résistance
  6. DimensionsDE, épaisseur de paroi
  7. Documents de contrôle et expéditionTouret et expédition
Essais et contrôleValeur d’essai / référenceFréquence
Essais individuels
Thermoelectric EMF calibration essai (IEC 60584-3)EMF deviation au sein de Class 1 (±1.5 °C / ±85 µV) à +100 °C / +200 °CChaque alliage fusion & production batch
1500 V / 2000 V AC diélectrique & polarity essai1 min AC withstand essai sans breakdownChaque fabriqué tambour

Certificat de contrôle

Délivré avec chaque touret, indiquant les résultats des essais individuels pour cette longueur.

Homologations du produit

IEC 60584-3 Class 1 & Class 2 CertifiedANSI/ISA MC96.1 & ASTM E230 CompliantCE, RoHS 2 (2011/65/EU) & REACH

Certificats de l’entreprise

ISO 9001ISO 14001ISO 45001Homologation VDEUL / cULCE · LVD / EMC

Marquage et livraison

Commande et livraison

Marquage de la gaine

TEBAOFLEX JX TYPE J EXTENSION <size> IEC 60584-3 CLASS 1 CE
Conditionnement de livraison
Non-returnable fumigated wooden tambours
Standard pas
500 m · 1000 m standard tambours (coupure pas sur demande)
Commande minimale
500 m (stock sections) · 1000 m (sur mesure)
Délai de livraison
2–4 weeks ex-travaille
Incoterms
EXW, FCA, FOB, CIF, DAP

Documents techniques

Téléchargements

Révision
2026-10-20
Mise à jour
2026-10-20

FAQ

Les premières questions des ingénieurs

Une autre question ? Envoyez votre plan — un ingénieur répond sous 2 heures ouvrées.

Why must care be taken non à confuse IEC 60584-3 et ANSI MC96.1 couleur codes sur Type JX câble?
À la fois standards utilisation un Blanc conducteur à l'intérieur d'un Noir gaine extérieure, but le polarity du Blanc fil est reversed! Sous IEC 60584-3, Positive (+) est Noir et Negative (−) est Blanc; sous ANSI MC96.1, Positive (+) est Blanc et Negative (−) est Rouge. Checking avec un électroaimant est foolproof: le Positive (+ Fe) Iron fil est always strongly magnetic.
Why does Type J utilisation un véritable extension câble (JX) rather que un compensating câble (JC)?
Because Iron (Fe) et Cuivre-Nickel (CuNi) sont already base metals, véritable thermocouple-qualité Fe/CuNi fils sont economical enough à utilisation pour le entire extension câble parcours, assurant Class 1 (±1.5 °C) accuracy sans needing un substitute compensating alliage.
CAN KCA (Fe/CuNi compensating câble pour Type K) be interchanged avec JX (Fe/CuNi extension câble pour Type J)?
Sans! Even though à la fois utilisation un Iron positive leg et un Cuivre-Nickel negative leg, le CuNi alliage composition dans KCA est specially formulated à match le ~40.6 µV/°C slope de Type K, whereas JX uses un 55Cu/45Ni alliage calibrated à le ~52.6 µV/°C slope de Type J .
How should le écran et drain fil de JX / Type J extension be earthed dans instrumentation et Ex-i boucles?
À empêcher circulating 50/60 Hz terre-boucle courants de coupling en millivolt ou 4–20 mA signaux, le Al/ PET écran et cuivre étamé drain fil de JX / Type J extension should be lié à le propre instrumentation terre bar à un extrémité uniquement (typically dans le commande/marshalling cabinet) et isolé contre chassis contact à le champ transmitter ou junction coffret, dans accordance avec IEC 60079-14 et EN 50288-7 .

Demander un devis

Obtenez un devis technique pour JX / Type J extension

Votre sélection et les détails de l’application sont copiés dans le formulaire ci-dessous.

01Dimensions sélectionnées

Utilisez + Ajouter à côté d’une dimension ou configuration.

02Enrouleur et mouvement

Ajoutez ici vos conditions de service pour les inclure dans votre demande.

03Message pour nos ingénieurs

JX / Type J extension Thermocouple Câble

Dimensions sélectionnées:


Enrouleur et mouvement:
- Type d’enrouleur: 
- Diamètre du noyau du tambour (mm): 
- Longueur de câble sur tambour (m): 
- Vitesse de déplacement (m/min): 
- Accélération maximale: 
- Cycles par heure: 
- Longueur et quantité: 
- Température ambiante: 
- Exposition (extérieur, eau, huile, abrasion): 
- Pays de destination: 
- Équipement et conditions de service: 