Instalación fija
Homologado para abierto tendido en J-hooks, bridal rings y cable bandejas portacables dentro de HVAC retorno-air plenums.
Producto
300 V UL 1424 / NFPA 262 plenum-nominal potencia-limited incendio alarm cable (18–12 AWG)
Valores típicos para este tipo de cable, basados en UL 1424 / NFPA 70 (NEC Art. 760) — confirmados en la ficha técnica y oferta de su pedido.
Aplicaciones
Type FPLP (Potencia-Limited Incendio Alarm Plenum Cable) está engineered a UL 1424 y NEC Article 760 para installation dentro de air-handling plenums, raised floors y environmental retorno-air ceiling conductos sin conducto, passing el rigorous NFPA 262 (UL 910) Steine
Homologado para abierto tendido en J-hooks, bridal rings y cable bandejas portacables dentro de HVAC retorno-air plenums.
Directo termination a UL 864 Incendio Alarm Control Panels (FACP), NAC extenders y voice amplifiers.
Substitutes para lower-hierarchy FPLR (riser) y FPL (general) cables en todos building zones.
Sólido ASTM B3 conductores de cobre desnudo se strictly para stationary building installation.
S07HXCHX-F apantallado flexiónConstrucción
Sólido desnudo conductor de cobre (ASTM B3, 18–12 AWG) + FEP /baja emisión de humos plenum aislamiento + opcional 100 % Al-Mylar pantalla con cobre estañado drenaje alambre + rojo baja emisión de humos plenum cubierta exterior + hilo de rasgado.
| # | Capa | Material y referencia |
|---|---|---|
| 1 | Sólido desnudo conductor de cobre | Sólido recocido sin recubrimiento cobre (18, 16, 14 o 12 AWG) según ASTM B3ASTM B3 |
| 2 | Plenum baja emisión de humos aislamiento | Etileno-propileno fluorado (FEP) o baja emisión de humos retardante de la llama plenum compuestoUL 1424 |
| 3 | Pantalla de lámina + drenaje (apantallado Tipos) | 100 % cobertura aluminio/poliéster cinta con 20–24 AWG cobre estañado trenzado drenaje alambreUL 1424 |
| 4 | Baja emisión de humos plenum cubierta | NFPA 262 compliant baja emisión de humos retardante de la llama PVDF o LS-PVC cubierta con nailon hilo de rasgado, Incendio Alarm RojoUL 1424 |
2C y 4C no apantallado cableados o pares trenzados para NAC horn/strobe circuitos y conventional detección.
100 % Al-Mylar Pantalla de lámina + cobre estañado drenaje alambre para addressable SLC datos lazos y 25/70 Vrms voice evac.
Datos técnicos
Dimensiones
Nominal dimensions, masses y eléctrico ratings para FPLP según a UL 1424 / NFPA 70 (NEC Art. 760).
| Designación | AWG & Conductores | Sección mm² | Ø ext. ≈ mm | Cobre kg/km | Peso total ≈ kg/km | Min. curvatura R fijo mm | Consulta |
|---|---|---|---|---|---|---|---|
| FPLP estándar serie | |||||||
| FPLP 18/2 Unshielded | 2C × 18 AWG | 0.82 mm² | 3.9 | 16 | 26 | 31 | |
| FPLP 18/4 Unshielded | 4C × 18 AWG | 0.82 mm² | 4.6 | 31 | 45 | 37 | |
| FPLP 16/2 Unshielded | 2C × 16 AWG | 1.31 mm² | 4.5 | 25 | 38 | 36 | |
| FPLP 16/4 Unshielded | 4C × 16 AWG | 1.31 mm² | 5.3 | 50 | 66 | 42 | |
| FPLP 14/2 Unshielded | 2C × 14 AWG | 2.08 mm² | 5.4 | 40 | 56 | 43 | |
| FPLP 14/4 Unshielded | 4C × 14 AWG | 2.08 mm² | 6.4 | 79 | 102 | 51 | |
| FPLP 12/2 Unshielded | 2C × 12 AWG | 3.31 mm² | 6.3 | 63 | 84 | 50 | |
| FPLP 18/2 Shielded OAS | 2C × 18 AWG OAS | 0.82 mm² | 4.1 | 19 | 30 | 33 | |
| FPLP 18/4 Shielded OAS | 4C × 18 AWG OAS | 0.82 mm² | 4.8 | 35 | 49 | 38 | |
| FPLP 16/2 Shielded OAS | 2C × 16 AWG OAS | 1.31 mm² | 4.7 | 28 | 42 | 38 | |
| FPLP 16/4 Shielded OAS | 4C × 16 AWG OAS | 1.31 mm² | 5.5 | 53 | 71 | 44 | |
| FPLP 14/2 Shielded OAS | 2C × 14 AWG OAS | 2.08 mm² | 5.6 | 43 | 61 | 45 | |
| FPLP 12/2 Shielded OAS | 2C × 12 AWG OAS | 3.31 mm² | 6.5 | 67 | 90 | 52 | |
| AWG & Conductores | Máx.. DC R @ 20 °C Ω/km | Corriente en air un | Corriente en conducto/bandeja un |
|---|---|---|---|
| 2C × 18 AWG | 21.400 | 7 | 6 |
| 4C × 18 AWG | 21.400 | 6 | 5 |
| 2C × 16 AWG | 13.500 | 10 | 9 |
| 4C × 16 AWG | 13.500 | 8 | 7 |
| 2C × 14 AWG | 8.450 | 15 | 13 |
| 4C × 14 AWG | 8.450 | 12 | 10 |
| 2C × 12 AWG | 5.310 | 20 | 17 |
| 2C × 18 AWG OAS | 21.400 | 7 | 6 |
| 4C × 18 AWG OAS | 21.400 | 6 | 5 |
| 2C × 16 AWG OAS | 13.500 | 10 | 9 |
| 4C × 16 AWG OAS | 13.500 | 8 | 7 |
| 2C × 14 AWG OAS | 8.450 | 15 | 13 |
| 2C × 12 AWG OAS | 5.310 | 20 | 17 |
Calidad y homologaciones
Ensayos de rutina en cada longitud de fabricación, ensayos de muestreo y tipo por lote — documentados en un certificado EN 10204 3.1.
| Ensayos e inspección | Valor de ensayo / referencia | Frecuencia |
|---|---|---|
| Ensayos de rutina | ||
| 1500 V AC dieléctrico ensayo & spark ensayo | Cero aislamiento breakdown según UL 1424 | 100 % de enrolladores |
| DC conductor resistencia & continuidad | Meets ASTM B3 sólido cobre limita a 20 °C | 100 % de enrolladores |
| Ensayos por muestreo | ||
| NFPA 262 (UL 910) Steiner Túnel plenum ensayo | Máx. llama spread ≤5.0 ft (1.52 m), peak óptico humo density ≤0.50, average ≤0.15 | UL Type FPLP listing |
Marcado y suministro
Marcado de la cubierta
Documentación técnica
Preguntas frecuentes
¿No está aquí? Envíenos su plano — un ingeniero responde en 2 horas laborables.
Solicitar presupuesto
La selección y los datos de aplicación se copian al formulario de consulta inferior.
Use + Añadir junto a una medida o configuración.
Añada aquí las condiciones de servicio para incluirlas en su consulta.