Engineered y verified para fixed service in accordance con IEC 62420 /IEC 62004.
Producto
GZTACSR Gap-Type Super-Thermal-Resistant aluminio Alloy Overhead conductor (GZTACSR) diseñado según IEC 62420 /IEC 62004 para Up a 500 kV AC servicio en -40 °C a +210 °C, con extra-high-strength galvanized acero core & gap y trapezoidal inner &
Valores típicos para este tipo de cable, basados en IEC 62420 /IEC 62004 — confirmados en la ficha técnica y oferta de su pedido.
Aplicaciones
GZTACSR Gap-Type Super-Thermal-Resistant aluminio Alloy Overhead conductor (GZTACSR) diseñado según IEC 62420 /IEC 62004 para Up a 500 kV AC servicio en -40 °C a +210 °C, con extra-high-strength galvanized acero core & gap y trapezoidal inner &
Engineered y verified para fixed service in accordance con IEC 62420 /IEC 62004.
Suitable para switchgear, control panels y equipment terminations within 20 × OD bend radius.
Use mechanical conduit o armado protection where exposed a rock fall o crushing loads.
Not designed para high-speed monospiral crane reeling; select a dedicated cable para enrollador.
NSHTOU cable para enrolladorConstrucción
Shown: GZTACSR (IEC 62420 /IEC 62004) con extra-high-strength galvanized acero core & gap, trapezoidal inner & round outer ztal layers y trapezoidal inner & round outer ztal layers (2-layer construcción).
| # | Capa | Material y referencia |
|---|---|---|
| 1 | Extra-high-strength galvanized acero core & gap | High-tensile galvanized acero core inside a heat-resistant grease-filled annular gapIEC 62420 /IEC 62004 |
| 2 | Trapezoidal inner & round outer ZTAL layers | Super-thermal-resistant zirconium-aluminio alloy (ZTAL) layers (+210 °C continuous)IEC 62420 /IEC 62004 |
Built a IEC 62420 /IEC 62004 con extra-high-strength galvanized acero core & gap y trapezoidal inner &
Full range of metric mm² y AWG/kcmil conductor sizes per IEC 62420 /IEC 62004
Supplied con EN 10204 3.1 routine dielectric & conductor resistance test certificate
Datos técnicos
Dimensiones
Manufactured a IEC 62420 /IEC 62004 in standard cross-sections from 50 mm² a 630 mm² (y North American AWG/kcmil code words).
| Designación de pedido | Nominal area | Cableado | Ø exterior ≈ mm | Peso ≈ kg/km | Tracción nominal kN ≈ | Min. sheave R mm | Consulta |
|---|---|---|---|---|---|---|---|
| GZTACSR Standard Transmission & Distribution Schedule (−40…+210 °C) | |||||||
| GZTACSR 50 mm² | 50 mm² | 7/3.00 mm | 9.0 | 138 | 14.5 | 180 | |
| GZTACSR 95 mm² | 95 mm² | 19/2.52 mm | 12.6 | 262 | 28.2 | 252 | |
| GZTACSR 120 mm² | 120 mm² | 19/2.85 mm | 14.3 | 334 | 36.4 | 286 | |
| GZTACSR 150 mm² | 150 mm² | 26/2.70 + 7/2.10 | 17.1 | 546 | 53.8 | 342 | |
| GZTACSR 185 mm² | 185 mm² | 26/3.00 + 7/2.33 | 19.0 | 674 | 65.2 | 380 | |
| GZTACSR 240 mm² | 240 mm² | 26/3.44 + 7/2.68 | 21.8 | 885 | 84.5 | 436 | |
| GZTACSR 300 mm² | 300 mm² | 26/3.86 + 7/3.00 | 24.5 | 1,110 | 104.2 | 490 | |
| GZTACSR 400 mm² | 400 mm² | 54/3.08 + 7/3.08 | 27.7 | 1,432 | 126.0 | 554 | |
| GZTACSR 500 mm² | 500 mm² | 54/3.44 + 7/3.44 | 31.0 | 1,790 | 156.5 | 620 | |
| GZTACSR 630 mm² | 630 mm² | 54/3.86 + 19/2.32 | 34.8 | 2,245 | 194.0 | 696 | |
| Nominal area | R₂₀ CC máx. Ω/km | Corriente continua A ≈ | Temp. de servicio |
|---|---|---|---|
| 50 mm² | 0.578 | 210 | −40…+210 °C |
| 95 mm² | 0.304 | 320 | −40…+210 °C |
| 150 mm² | 0.192 | 435 | −40…+210 °C |
| 240 mm² | 0.119 | 590 | −40…+210 °C |
| 400 mm² | 0.072 | 820 | −40…+210 °C |
| 630 mm² | 0.046 | 1,080 | −40…+210 °C |
Calidad y homologaciones
Ensayos de rutina en cada longitud de fabricación, ensayos de muestreo y tipo por lote — documentados en un certificado EN 10204 3.1.
| Ensayos e inspección | Valor de ensayo / referencia | Frecuencia |
|---|---|---|
| Ensayos de rutina | ||
| conductor DC resistance & dimensional verification (IEC 62420 /IEC 62004) | DC resistance at 20 °C y geometry within IEC 62420 /IEC 62004 class limits | Every manufactured drum / spool |
| Routine dielectric / spark / structural integrity test (IEC 62420 /IEC 62004) | Zero breakdown o structural defect over full production length | Every manufactured drum / spool |
| Ensayos por muestreo | ||
| Thermal aging, mechanical & material qualification (IEC 62420 /IEC 62004) | Full compliance con IEC 62420 /IEC 62004 across −40…+210 °C | Type qualification & periodic sample audit |
Marcado y suministro
Marcado de la cubierta
Documentación técnica
Preguntas frecuentes
¿No está aquí? Envíenos su plano — un ingeniero responde en 2 horas laborables.
Solicitar presupuesto
La selección y los datos de aplicación se copian al formulario de consulta inferior.
Use + Añadir junto a una medida o configuración.
Añada aquí las condiciones de servicio para incluirlas en su consulta.